| 2019-05-23 16:40:33 | ***CORRECTIONS*** |
| | PETER E VALENTI |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6673 |
| | |
| | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| | FBC B = FBC BUILDING |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | FBC R = FBC RESIDENTIAL |
| | |
| | BUILDING PLAN REVIEW (1ST REVIEW) DENIED: |
| | |
| | FBC B 107: THE SUBMITTED PLANS ARE NOT COMPLETE. PLEASE |
| | PROVIDE THE FOLLOWING: |
| | |
| | 1. A SURVEY APPROVED BY A LICENSED SURVEYOR COMPLETE |
| | WITH PROPOSED LOCATION OF HOUSE, ELEVATIONS, SETBACKS, |
| | AND ALL OTHER REQUIRED INFORMATION. |
| | 2. A SITE PLAN PAGE AS PART OF THE PLANS. |
| | 3. DESIGNER OF RECORD SIGNATURES AND SEALS ON ALL PAGES |
| | PER THE FLORIDA STATE STATUTES CHAPTER 471/FL ADMIN. |
| | RULES 61G15-23.001 TO 61G15-23.003 AND CHAPTER 481/FL |
| | ADMIN. RULE 61G1-16.004. |
| | 4. MORE INFORMATION ON THE EXISTING SITE; IT APPEARS |
| | THAT THERE IS AN EXISTING STRUCTURE ON THIS LOT AND |
| | THERE ARE NO INDICATIONS OF A DEMO PERMIT ON RECORD. |
| | PLEASE CLARIFY. |
| | 5. A WINDOW/DOOR SUBMITTAL WITH PRODUCT APPROVALS. |
| | 6. THE PRODUCT AND CONNECTION DETAILS ARE REQUIRED FOR |
| | REINFORCING STEEL (SCREW-IN) CONNECTIONS BETWEEN WALLS |
| | AND SLAB. |
| | 7. THE PLAN DESIGN AND NOTES NEED TO BE REVIEWED, |
| | UPDATED TO THE CURRENT CODE (2017 SIXTH EDITION OF THE |
| | FLORIDA BUILDING CODE) AND APPROVED. |
| | 8. THE DETAILS THAT DO NOT RELATE TO THIS SPECIFIC |
| | PROJECT NEED TO BE DELETED FROM PLAN PAGES. |
| | |
| | |
| | NOTES: |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL COMMENTS MAY |
| | RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY |
| | REVIEWED SHEETS DETACHED. |
| | |
| | |