2019-05-07 15:34:18BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 JOSEAN A. DUPREY E.I., BN, PX
 BUILDING PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6716
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. THE REQUIRED UPLIFT PRESSURE FOR ZONE 3 IS -111PSF.
 THE PRODUCT SELECTED IS DESIGN FOR A MAXIMUN UPLIFT
 PRESSURE OF -90PSF. PER PRODUCT APPROVAL LIMITATION 5.7
 ZONE 3 SHALL EMPLOY AN ATTACHMENT DENSITY DESIGNED BY A
 QUALIFIED DESIGN PROFESSIONAL TO RESIST THE ELEVATED
 PRESSURE CRITERIA. PLEASE PROVIDE THE ANHANCEMENT
 ATTACHEMENTS PATERN FOR ZONE 3. FBC 107, FBC 1609