| 2019-05-13 10:41:32 | 1ST REVIEW: 19050158 |
| | |
| | 2017 FLORIDA BUILDING CODE 6TH EDITION |
| | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| | EDITION |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. SHT 1 OF 1 PLEASE SHOW EXISTING PLUMBING FIXTURES ON |
| | DEMO PLAN. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 2. THE VALUATION OF THE PROJECT SEEMS LOW PLEASE |
| | PROVIDE A DETAILED, QUANTITY ESTIMATES, AND/OR BONA |
| | FIDE SIGNED CONTRACTS (EXCLUDING LAND VALUE) TO MEET |
| | THE |
| | APPROVAL OF THE BUILDING OFFICIAL.PER WPB AMEND TO FBC |
| | 109.3 |
| | |
| | 3. ON THE SANITARY ISOMETRIC DRAWING THE WASHING |
| | MACHINE AND LAUNDRY SINK SHALL CONNECT TO THE BUILDING |
| | DRAIN DOWN STREAM OF THE BATHROOM GROUP ONLY THE |
| | FIXTURES IN THE BATHROOM GROUP CAN CINNECT TO THE WET |
| | VENT SYSTEM FOR THE BATHROOM GROUP. PER FBC RES P3108 |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |
| | |