| Plan Review Notes For Permit 19050129 |
| Permit Number |
19050129 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-05-10 11:59:30 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | | INSPECTION. | | | | | | | | | | | | 1) SHEET D 1.1 - THERE IS AN INCORRECT REFERENCE TO THE | | | FFPC (5TH). | | | | | | THE CORRECT EDITION IS 6TH. | | | | | | PLEASE TAKE NOTE, ENSURE COMPLIANCE. | | | | | | | | | | | | 2) SHEET A 1.2 - THERE IS INDICATIONS OF PAINTING OF | | | WALLS AND CEILING. | | | | | | PLEASE ENSURE NOT TO PAINT SPRINKLER HEADS AND FIRE | | | ALARM DEVICES. | | | | | | | | | | | | 3) THE FIRE SPRINKLER AND FIRE ALARM SYSTMES SHALL | | | REMAIN ACTIVE AND FUCNTIONAL AT ALL TIMES. | | | | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | | | | |
|