| 2019-08-27 11:04:23 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| | FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION |
| | NFPA 54 = NATIONAL FUEL GAS CODE |
| | NFPA 58 = LIQUIFIED PETROLEUM GAS CODE |
| | NFPA 96 = STANDARD FOR VENTILATION CONTROLAND FIRE |
| | PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017 |
| | NFPA 99 = HEALTH CARE FACILITIES CODE |
| | NFPA 99B = STANDARD FOR HYPERBARIC FACILITIES |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | |
| | 2ND REVIEW |
| | PLUMBING COMMEMTS: DENIED |
| | |
| | 1. REGARDING THE SECOND FLOOR WOMEN?S RESTROOM; PER FBC |
| | PL 905.3 AND 904.5.4, VERY DRY VENT CONNECTING TO A |
| | HORIZONTAL DRAIN SHALL CONNECT ABOVE THE CENTERLINE OF |
| | THE HORIZONTAL DRAIN PIPE AND SHALL RISE VERTICALLY TO |
| | A POINT NOT LESS THAN 6 INCHES (152 MM) ABOVE THE FLOOD |
| | LEVEL RIM OF THE HIGHEST TRAP OR TRAPPED FIXTURE BEING |
| | VENTED. THE DRY VENT IN THIS SITUATION IS OFFSETTING |
| | HORIZONTALLY BELOW THE FLOOR AS OPPOSED TO RISING |
| | VERTICALLY TO THE POINT OF 6? ABOVE THE FLOOD LEVEL RIM |
| | OF THE HIGHEST FIXTURE BEING SERVED. PER WPB FBC |
| | 107.2.1, CORRECT ON BOTH P1.0 AND P2.0. |
| | |
| | 2. REGARDING THE FIRST FLOOR MEN?S RESTROOM; PER FBC PL |
| | 905.3 AND 904.5.4, EVERY DRY VENT CONNECTING TO A |
| | HORIZONTAL DRAIN SHALL CONNECT ABOVE THE CENTERLINE OF |
| | THE HORIZONTAL DRAIN PIPE AND SHALL RISE VERTICALLY TO |
| | A POINT NOT LESS THAN 6 INCHES (152 MM) ABOVE THE FLOOD |
| | LEVEL RIM OF THE HIGHEST TRAP OR TRAPPED FIXTURE BEING |
| | VENTED. THE DRY VENT IN THIS SITUATION IS A CIRCUIT |
| | VENT FOR THE THREE WATER CLOSETS ON THE VENTED BRANCH |
| | WHICH EXTENDS HORIZONTALLY BELOW THE FLOOR TO THE |
| | NEAREST WALL BEFORE RISING VERTICALLY AS OPPOSED TO |
| | CONNECTING ABOVE THE CENTERLINE OF THE DRAIN, RISING |
| | VERTICALLY TO THE POINT OF 6? ABOVE THE FLOOD LEVEL RIM |
| | OF THE HIGHEST FIXTURE BEING SERVED. PER WPB FBC |
| | 107.2.1, CORRECT ON BOTH P1.0 AND P2.0. |
| | |
| | 3. PER FBC ACC 604.7, TOILET PAPER DISPENSERS SHALL |
| | COMPLY WITH 309.4 AND SHALL BE 7 INCHES (180 MM) |
| | MINIMUM AND 9 INCHES (230 MM) MAXIMUM IN FRONT OF THE |
| | WATER CLOSET MEASURED TO THE CENTERLINE OF THE |
| | DISPENSER. SEE RED LINED PROVISO ON PLAN SHEET |
| | A-2.0/DETAIL 15. |
| | |
| | 4. PER FBC ACC 604.2, THE WATER CLOSET SHALL BE |
| | POSITIONED WITH A WALL OR PARTITION TO THE REAR AND TO |
| | ONE SIDE. THE CENTERLINE OF THE WATER CLOSET SHALL BE |
| | 16 INCHES (405 MM) MINIMUM TO 18 INCHES (455 MM) |
| | MAXIMUM FROM THE SIDE WALL OR PARTITION. SEE RED LINED |
| | PROVISO ON PLAN SHEET A-2.0/DETAIL 5. |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED |
| | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | |
| | |
| | |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | PHONE 561-805-6715 |
| | |
| | 19050125 810 CHARLOTTE AVE |
| | |