Plan Review Notes
Plan Review Notes For Permit 19050125
Permit Number 19050125
Review Stop P
Sequence Number 2
Notes
Date Text
2019-08-27 11:04:23CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 NFPA 54 = NATIONAL FUEL GAS CODE
 NFPA 58 = LIQUIFIED PETROLEUM GAS CODE
 NFPA 96 = STANDARD FOR VENTILATION CONTROLAND FIRE
 PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017
 NFPA 99 = HEALTH CARE FACILITIES CODE
 NFPA 99B = STANDARD FOR HYPERBARIC FACILITIES
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 2ND REVIEW
 PLUMBING COMMEMTS: DENIED
  
 1. REGARDING THE SECOND FLOOR WOMEN?S RESTROOM; PER FBC
 PL 905.3 AND 904.5.4, VERY DRY VENT CONNECTING TO A
 HORIZONTAL DRAIN SHALL CONNECT ABOVE THE CENTERLINE OF
 THE HORIZONTAL DRAIN PIPE AND SHALL RISE VERTICALLY TO
 A POINT NOT LESS THAN 6 INCHES (152 MM) ABOVE THE FLOOD
 LEVEL RIM OF THE HIGHEST TRAP OR TRAPPED FIXTURE BEING
 VENTED. THE DRY VENT IN THIS SITUATION IS OFFSETTING
 HORIZONTALLY BELOW THE FLOOR AS OPPOSED TO RISING
 VERTICALLY TO THE POINT OF 6? ABOVE THE FLOOD LEVEL RIM
 OF THE HIGHEST FIXTURE BEING SERVED. PER WPB FBC
 107.2.1, CORRECT ON BOTH P1.0 AND P2.0.
  
 2. REGARDING THE FIRST FLOOR MEN?S RESTROOM; PER FBC PL
 905.3 AND 904.5.4, EVERY DRY VENT CONNECTING TO A
 HORIZONTAL DRAIN SHALL CONNECT ABOVE THE CENTERLINE OF
 THE HORIZONTAL DRAIN PIPE AND SHALL RISE VERTICALLY TO
 A POINT NOT LESS THAN 6 INCHES (152 MM) ABOVE THE FLOOD
 LEVEL RIM OF THE HIGHEST TRAP OR TRAPPED FIXTURE BEING
 VENTED. THE DRY VENT IN THIS SITUATION IS A CIRCUIT
 VENT FOR THE THREE WATER CLOSETS ON THE VENTED BRANCH
 WHICH EXTENDS HORIZONTALLY BELOW THE FLOOR TO THE
 NEAREST WALL BEFORE RISING VERTICALLY AS OPPOSED TO
 CONNECTING ABOVE THE CENTERLINE OF THE DRAIN, RISING
 VERTICALLY TO THE POINT OF 6? ABOVE THE FLOOD LEVEL RIM
 OF THE HIGHEST FIXTURE BEING SERVED. PER WPB FBC
 107.2.1, CORRECT ON BOTH P1.0 AND P2.0.
  
 3. PER FBC ACC 604.7, TOILET PAPER DISPENSERS SHALL
 COMPLY WITH 309.4 AND SHALL BE 7 INCHES (180 MM)
 MINIMUM AND 9 INCHES (230 MM) MAXIMUM IN FRONT OF THE
 WATER CLOSET MEASURED TO THE CENTERLINE OF THE
 DISPENSER. SEE RED LINED PROVISO ON PLAN SHEET
 A-2.0/DETAIL 15.
  
 4. PER FBC ACC 604.2, THE WATER CLOSET SHALL BE
 POSITIONED WITH A WALL OR PARTITION TO THE REAR AND TO
 ONE SIDE. THE CENTERLINE OF THE WATER CLOSET SHALL BE
 16 INCHES (405 MM) MINIMUM TO 18 INCHES (455 MM)
 MAXIMUM FROM THE SIDE WALL OR PARTITION. SEE RED LINED
 PROVISO ON PLAN SHEET A-2.0/DETAIL 5.
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  
 19050125 810 CHARLOTTE AVE
  