| 2019-06-04 16:09:26 | PLUMBING 1ST REVIEW**DENIED** |
| | |
| | 1-ALL SHEETS SHALL BE SIGNED BY DESIGN PROFESSIONAL. |
| | ONLY THE MEP?S ARE SIGNED AND SEALED. F.S 471, 481 |
| | |
| | 2- WHERE THE DEVELOPED LENGTH OF THE HOT WATER SYSTEM |
| | IS OVER 50? A RECIRCULATING SYSTEM SHALL INSTALLED INTO |
| | THE SYSTEM. FBC-P 607.2 |
| | |
| | 3- PROVIDE LOCATION AND ACCESS FOR TRAP PRIMER DEVICES. |
| | IT APPEARS THAT THE TRAP PRIMER DEVICE WILL BE IN THE |
| | WALL BETWEEN THE 2 SHOWERS AND NOT SERVICEABLE. FBC |
| | 107.2.1 |
| | |
| | 4-ALL THE TOILET LESS THE 1ST FLOOR MEN?S ARE DRY |
| | VENTED ON BOTH FLAT AND ISOMETRIC DRAWING. FBC-P 912.2 |
| | |
| | 5- SHT. P1.0 AND A2.0 SHOW THE ACCESSIBLE SHOWER VALVES |
| | LOCATED ON THE INCORRECT WALL. FBC-ACC 608.5 |
| | |
| | 6- PROVIDE MEASUREMENT FOR MIRRORS BEING MAX 40? FROM |
| | THE REFLECTIVE SURFACE. FBC-ACC 603.3 |
| | |
| | 7-ADD NOTE THAT ALL HAND SINKS SHALL BE TEMPERED TO MAX |
| | 110F BY AN APPROVED ASSE 1070 DEVICE. FBC-P 607.1.2 |
| | |
| | 8- SHOW DETAIL SIDE GRAB BAR AS 54? OVERALL AND REAR |
| | GRAB BAR AS 36? OVERALL AND MOUNT 12? FROM CENTER OF |
| | TOILET TOWARDS THE SIDE WALL. FBC-ACC 604.5 |
| | |
| | 9- 1ST FLOOR FEMALE AND 2ND FLOOR MEN?S AND WOMEN?S |
| | RESTROOM?S ARE MISSING THE LAVATORY IN THE TOILET |
| | COMPARTMENT. WHERE A TOILET ROOM / COMPARTMENT IS |
| | PROVIDED IT SHALL COMPLY WITH FBC-ACC 213** (CORRECTED |
| | FROM 231 ON 6/25/19), 604.8.1.6 |
| | |
| | 10- SHT A2.09 DETAIL # 3, 15, 17 SHT A2.1 DETAIL 26 AND |
| | 28 SHOW THE HEIGHT OF THE LAVATORIES TO BE 48?. MAX |
| | PERMITTED IS 34? FBC-ACC 606.3 AND AS YOU CALL YOU ON |
| | SHT. A3.0. PLEASE CORRECT OR CLARIFY. |
| | |
| | 11- ADD NOTE ALL HOT WATER PIPING AND RETURN PIPING |
| | SHALL BE INSULATED PER TABLE C404.6 OF THE FBC-ENERGY |
| | CODE. FBC-P 607.2.1, 607.5 |
| | |
| | 12- THE 2ND FLOOR MEN?S RESTROOM SHOWS 2 URINALS. ONE |
| | SHALL BE ACCESSIBLE. PROVIDE CLEAR FLOOR SPACE ON SHT. |
| | A-1.1. FBC-ACC 213, 605.3 |
| | |
| | |
| | TIM HUNT |
| | PLUMBING INSPECTOR/ PLUMBING PLANS EXAMINER |
| | BUILDING DIVISION |
| | CITY OF WEST PALM BEACH |
| | 561-248-2703 |