Plan Review Notes
Plan Review Notes For Permit 19050125
Permit Number 19050125
Review Stop B
Sequence Number 1
Notes
Date Text
2019-06-19 14:18:34BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
  
 06/25/19 NEW COMMENT:
 THERE ARE SEVERAL BUILDINGS ON THIS PROPERTY. PERMIT
 APPLICATION IDENTIFIES THIS BUILDING AS 801 CHARLOTTE
 AVE. THIS ADDRESS IS INCORRECT. ODD NUMBERS SHOULD BE
 ON THE OTHER SIDE OF THE STREET. REVISE AS REQUIRED.
 PLEASE PROVIDE EXACT ADDRESS FOR BUILDING WHERE WORK IS
 TAKING PLACE. REVISE ADDRESS ON ALL DRAWINGS. ADDRESS
 WAS CHANGED TO 810 CHARLOTTE AVE IN OUR SYSTEM. PLEASE
 COORDINATE WITH US TO BEST IDENTIFY THE BUILDING WHERE
 WORK IS TAKING PLACE. . SEC. 107.2.1 CITY AMENDMENTS.
  
  
 NOTE: SEC. 801.3 FBC-EXISTING BUILDING. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1- ARCHITECT OF RECORD TO SIGN AND SEAL ALL
 PLANS/DOCUMENTS AS REQUIRED BY CHAPTER 481 F.S. WHEN
 SUBMITTING PLANS/DOCUMENTS FOR PUBLIC RECORDS.
  
 2- MEN'S AND WOMEN'S RESTROOMS USED TO HAVE TOILET
 COMPARTMENTS WITH WATER CLOSET AND LAVATORY. PROPOSED
 RESTROOMS SEEM TO BE LESS ACCESSIBLE THAN WHAT IT WAS
 BEFORE. FIRST FLOOR WOMEN'S RESTROOM AND BOTH RESTROOMS
 ON THE SECOND FLOR DON'T HAVE THE TOILET COMPARTMENT
 WITH A LAVATORY. SHOW COMPLIANCE WITH SEC. 604.8.1.6
 AND SEC. 604.8.1.7 FBC ACCESSIBILITY. NOTE: SEE ALSO,
 ADVISORY 604.8.1.6 AND 604.8.1.7 FBC-ACCESSIBILITY.
  
 3-1ST FLOOR PLAN ON SHEET A-1.0:
 A)ENTRANCE TO THE SHOWER'S AREA IN THE MEN'S RESTROOM
 DOESN'T COMPLY WITH THE CLEAR WIDTH REQUIRED BY SEC.
 403.5.1 FBC-ACCESSIBILITY. REVISE AS REQUIRED. PLAN
 SHOWS 2'6". REVISE AS REQUIRED.
  
 B)PROVIDE THE CLEAR DIMENSION TO ENTER THE MEN'S LOCKER
 AREA. SEC. 403.5.1 FBC-ACCESSIBILITY.
  
 C)THE DOORS ON THE FOYER AREA OF BOTH RESTROOMS DON'T
 COMPLY WITH THE DOORS IN SERIES DISTANCE REQUIRED BY
 SEC. 404.2.6 FBC-ACCESSIBILITY. REVISE AS REQUIRED.
  
 D) MEN'S SHAVING STATION. SHOW COMPLIANCE WITH COUNTER
 WORK SURFACE. SEC. 902 FBC-ACCESSIBILITY AND MIRROR
 SEC. 603.3 FBC-ACCESSIBILITY.
  
 E) WOMEN'S MAKE UP STATION. SHOW COMPLIANCE WITH
 COUNTER WORK SURFACE. SEC. 902 FBC-ACCESSIBILITY AND
 MIRROR SEC. 603.3 FBC-ACCESSIBILITY.
  
 F)HANDICAPPED BENCH IN THE MENS' RESTROOM:
 (1)DON'T SEEM TO PROVIDE PRIVACY. SEC. 803.1
 FBC-ACCESSIBILITY. SEE ADVISORY FOR SEC. 803.1
 FBC-ACCESSIBILITY.
  
 (2) THE HANDICAPPED BENCH CLEAR FLOOR SPACE REQUIRED BY
 SEC. 903.2 FBC-ACCESSIBILITY IS BLOCKING THE
 ACCESS/EGRESS FROM SHOWER AREA.
  
 (3)PROVIDE SPECS FOR BENCH AS REQUIRED BY SEC. 903.4
 FBC-ACCESSIBILITY. SHOW COMPLIANCE WITH ALL THE
 REQUIREMENTS OF SEC. 903 FOR BENCHES.
  
 NOTE: CLARIFY WOMEN DON'T HAVE ANY SPECS FOR
 HANDICAPPED BENCH. SEC. 803.4 FBC-ACCESSIBILITY.
  
 G) MEN'S LOOKERS AREA DON'T HAVE TURNING SPACE. SEC.
 803.2 FBC-ACCESSIBILITY
  
 H) THE MENS' RESTROOM ENTRY DOOR LOCATED BY THE URINALS
 AREA DON'T COMPLY WITH THE MANEUVERING CLEARANCE
 REQUIRED BY SEC. 404.2.4 FBC-ACCESSIBILITY ON THE PULL
 SIDE OF THE DOOR. NEED 18" MIN. REVISE AS REQUIRED.
  
 I)THERE IS A NOTE BY THE LOCKERS AREA STATING "SEE DTL.
 IN SHEET A.4.0" FOR THE LOCKER DETAILS. THERE IS NOT
 SHEET A-4.0. REVISE AS REQUIRED. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE, INSERT CORRECTED PAGES INTO THE SUBMITTAL AND
 REMOVE/VOID THE PREVIOUSLY REVIEWED SHEETS. PLEASE
 DON'T STAPLE OLD DRAWINGS/DOCUMENTS . SUBMIT OLD
 DRAWINGS/DOCUMENTS FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  