| Date |
Text |
| 2019-08-26 15:24:16 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | FAC = FLORIDA ADMINISTRATIVE CODE |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. PROVIDE LOAD CALCULATION FOR 400 AMP SERVICE. THE |
| | PANEL SCHEDULE SHOWS 3 TRAILERS. SHEET 5 SHOWS THAT |
| | THERE ARE 2 PANELS, PANEL A AND PANEL B. IS THIS 2 OF |
| | THE 3 TRAILERS, OR IS THIS CONSIDERED ONE TRAILER |
| | BECAUSE IT IS JOINED TOGETHER? PROVIDE CLARIFICATION. |
| | NEC 215.2, 220, 408.30; WPB FBC 107.2.1 |
| | 2. RISER DIAGRAM DOES NOT SHOW WIRE SIZES TO TRAILER |
| | PANELS. PROVIDE CORRECTION. NEC 215.5, 310.159B)(16); |
| | WPB FBC 107.2.1 |
| | 3. RISER DIAGRAM SHOWS A SINGLE GROUND ROD AS A |
| | SUPPLEMENTAL GROUNDING ELECTRODE. THIS SUPPLEMENTAL |
| | GROUNDING ELECTRODE NEEDS TO BE AUGMENTED BY AN |
| | ADDITIONAL ELECTRODE AT LEAST 6 FEET AWAY OR PROVIDE |
| | EVIDENCE OF RESISTANCE TO GROUND OF 25 OHMS OR LESS. |
| | NEC 250.53(A)(2) |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| | SHEETS. |
| | |
| | SINCERELY, |
| | |
| | JOHN PEARSON |
| | ELECTRICAL PLANS EXAMINER |
| | 561-805-6746 |
| | [email protected] |
| | |