| 2019-08-26 08:12:22 | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 19050124 |
| | ADD: 2201 45TH STREET JFK NORTH |
| | CONT: DPR CONSTRUCTION |
| | TEL: 954-991-6200 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION. |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: MON. AUGUST 26, 2019 |
| | ACTION: DENIED |
| | |
| | ********************************4X FEE / NOTICE!!!!! |
| | FLORIDA STATUTE 553.80(2)(B) |
| | ************************************************** |
| | WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS? |
| | DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN |
| | ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING |
| | CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS |
| | REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO |
| | CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY |
| | NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, |
| | EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY, |
| | ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL, |
| | MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER |
| | REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING |
| | COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL |
| | GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH |
| | REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION, |
| | A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE |
| | PERMIT FEE ATTRIBUTED TO PLANS REVIEW. |
| | |
| | 1) 2ND REQUEST. THE SUBMITTED PLANS MODULAR STRUCTURES |
| | FOR WILLIAM SCOTSMAN FOR A 36 FT. X 56 FT. MODULAR UNIT |
| | DOES NOT SHOW A 3RD PARTY REVIEW. GENERAL NOTE 20 |
| | STATES THE RAISED SEAL SET OF PLANS ARE ON FILE IN THE |
| | THIRD PARTY AGENCY'S OFFICE AS DIRECTED BY DCA. |
| | IN THE DBPR WEBSITE FOR MANUFACTURED BUILDINGS THERE IS |
| | PLANS FOR WILLIAM SCOTSMAN AS THE MANUFACTURER (THERE |
| | ARE DIFFERENT QUALIFIERS, SPECIFY WHICH QUALIFIER) AND |
| | MODULAR PLANS DESIGN, CO. AS THE APPROVING AGENCY. |
| | PLEASE PROVIDE THE AGENCY PLAN APPROVAL NUMBER. |
| | |
| | IF THERE IS NO 3RD PARTY APPROVAL FOR THESE PLANS, THEY |
| | THEN ARE NOT APPROVED BY THE STATE AND WILL NEED TO BE |
| | UPDATED TO THE 2017 FBC-B AND EACH PAGE WILL NEED TO BE |
| | SIGNED AND SEALED ELECTRONICALLY. |
| | THE STATE PLAN ARE STILL AVAILABLE ON LINE AND CAN BE |
| | REVIEWED WHEN CONTACTING THE AGENCY. |
| | THE COVERSHEET LIST THOMAS L. MELTON AS THE CONSULTING |
| | ARCHITECT. PLEASE SHOW COMPLIANCE WITH THE FLORIDA |
| | ADMINISTRATIVE CODE. ARCHITECT DIGITAL SIGNING & |
| | SEALING PLANS. 61G1-16.005 PROCEDURES FOR DIGITALLY |
| | SIGNING AND SEALING AND FOR ELECTRONICALLY TRANSMITTING |
| | PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS. |
| | |
| | 2) 2ND REQUEST. THE COVERSHEET STATES THIS BUILDING IS |
| | NOT TO BE PLACED IN A FLOOD ZONE. THE SITE PLAN SHOWS |
| | WHERE THE PROPOSED BUILDING IS TO BE PLACED IS IN AN AE |
| | FLOOD ZONE WITH A BFE OF 12.00 FT. NAVD88. PLEASE SHOW |
| | HOW COMPLIANCE WITH THE BOTTOM OF THE MANUFACTURED |
| | BUILDING WILL BE ABOVE THE BASE FLOOD PLUS THE |
| | ADDITIONAL 2 FEET REQUIRED BY THE CITY OF WEST PALM |
| | BEACH MUNI CODE SECTION ARTICLE XVII ORDINANCES ARTICLE |
| | XVII FLOOD PREVENTION & CONTROL. |
| | |
| | DURING THE PERMITTING OF THIS STRUCTURE THERE WILL BE |
| | REQUIRED (3) DIFFERENT FLOOD ZONE CERTIFICATES |
| | REQUIRED: |
| | (1) A FLOOD ZONE CERTIFICATE IS REQUIRED AS PART OF THE |
| | PLAN REVIEW DOCUMENTS WITH THE PROPOSED FINISH FLOOR |
| | HEIGHT. W. P. B. ADMINISTRATIVE CODE 107.3.5.1.1 |
| | BUILDING MINIMUM PLAN REVIEW CRITERIA FOR COMMERCIAL |
| | BUILDINGS. (8) FLOOD REQUIREMENTS ELEVATIONS, |
| | ENCLOSURES, FLOOD DAMAGE-RESISTANT MATERIALS. |
| | (2) ONCE THE FIRST FLOOR SLAB IS POURED THE 2ND |
| | ELEVATION CERTIFICATE IS REQUIRED. W. P. B. |
| | ADMINISTRATIVE CODE 110.3 REQUIRED INSPECTIONS 1.2 |
| | FLOOR/ SLAB INSPECTION. IN FLOOD HAZARD AREAS, UPON |
| | PLACEMENT OF THE LOWEST FLOOR, INCLUDING BASEMENT, AND |
| | PRIOR TO FURTHER VERTICAL CONSTRUCTION, THE ELEVATION |
| | CERTIFICATION, REQUIRED IN SECTION 1612.5, SHALL BE |
| | SUBMITTED TO THE BUILDING OFFICIAL. |
| | (3) BEFORE THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY |
| | OR A CERTIFICATE OF COMPLETION THE 3RD FLOOD ZONE |
| | CERTIFICATE IS REQUIRED WITH THE HEIGHT OF ALL EXTERIOR |
| | ATTENDANTS A/C PADS OR OTHER SLABS FOR GENERATORS. |
| | W. P. B. ADMINISTRATIVE CODE 110.3 REQUIRED INSPECTIONS |
| | (6) FINAL INSPECTION. TO BE MADE AFTER THE BUILDING IS |
| | COMPLETED AND READY FOR OCCUPANCY. 6.1. LOWEST FLOOR |
| | ELEVATION. IN FLOOD HAZARD AREAS, AS PART OF THE FINAL |
| | INSPECTION, A FINAL CERTIFICATION OF THE LOWEST FLOOR |
| | ELEVATION SHALL BE SUBMITTED TO THE AUTHORITY HAVING |
| | JURISDICTION. |
| | |
| | FEMA NEW FORM AVAILABLE JUNE 13/2016. |
| | OMB NO. 1660-0008 |
| | EXPIRATION DATE: NOV. 30/2018 |
| | HTTP://WWW.FEMA.GOV/BUSINESS/NFIP/ELVINST.SHTM |
| | |
| | 3) COMPLIED. |
| | |
| | 4) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER BN, PX, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | |