| 2019-05-03 11:09:30 | RESIDENTIAL (R3) BUILDING REVIEW COMMENTS |
| | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| | |
| | 1- FLAT ROOF NOA 18-0919.12 SUBMITTED: CLEARLY MARK |
| | WHICH APPROVED ASSEMBLY IS GOING TO BE INSTALLED TO |
| | VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. |
| | R301.1 FBC-RESIDENTIAL. NOTE: IF THE SELECTED ASSEMBLY |
| | DOESN'T MEET THE DESIGN PRESSURES FOR ALL ROOF ZONES, |
| | THEN SIGNED AND SEALED RAS 117 CALCULATIONS ARE |
| | REQUIRED. SEE GENERAL LIMITATION #7 ON LAST PAGE OF |
| | NOA. |
| | ASSEMBLIES THAT ARE LIMITED BY GENERAL LIMITATION #9 |
| | MAY NOT BE USED IF THE MAXIMUM DESIGN PRESSURES DON'T |
| | MEET THE DESIGN PRESSURES FOR ALL ROOF ZONES. GENERAL |
| | LIMITATION #9 DOESN'T ALLOW NAIL ENHANCEMENT. SEE |
| | GENERAL LIMITATION #9 ON LAST PAGE OF NOA. |
| | |
| | 2- ROOF TILE NOA 18-0509.15 SUBMITTED: CLEARLY MARK |
| | ROOF TILE FASTENING METHOD AS REQUIRED BY CITY POLICY |
| | FOR ALL ROOFING PERMITS. |
| | |
| | 3- ROOF TILE ADHESIVE NOA 17-0322.03 SUBMITTED: CLEARLY |
| | MARK PADDY SIZE AS REQUIRED BY CITY POLICY FOR ALL |
| | ROOFING PERMITS. |
| | |
| | 4- POLYGLASS UNDERLAYMENT NOA 17-0614.22 SUBMITTED: |
| | CLEARLY IDENTIFY WHICH INSTALLATION PROCEDURE FROM PAGE |
| | 4 OF 8 IS GOING TO BE INSTALLED AS REQUIRED BY CITY |
| | POLICY FOR ALL ROOFING PERMITS. |
| | |
| | 5- CONTRACTOR NEEDS TO SPECIFY ON THE PERMIT |
| | APPLICATION THE ROOF AREA (FLAT ROOF AREA AND PITCH |
| | ROOF AREA), ROOF PITCH AND MEAN ROOF HEIGHT AS REQUIRED |
| | BY CITY POLICY FOR ALL ROOFING PERMITS. |
| | |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | PLEASE, INSERT CORRECTED PAGES INTO THE SUBMITTAL AND |
| | REMOVE/VOID THE PREVIOUSLY REVIEWED SHEETS. |
| | PLEASE DON'T STAPLE OLD DRAWINGS/DOCUMENTS . SUBMIT OLD |
| | DRAWINGS/DOCUMENTS FOR REFERENCE. |
| | |