| Plan Review Notes For Permit 19050028 |
| Permit Number |
19050028 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2020-08-02 15:10:12 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | IS THIS A PLAN FOR A GENERATOR OR A REVISION THEY ARE | | | TWO SEPARATE ITEMS? PERMIT IS FOR A GENERATOR. | | | | | | PAGE SUBMITTED BY CONTRACTOR HAS TO BE STAMPED BY | | | ENGINEER OF RECORD. | | | | | | PAGE SUBMITTED BY CONTRACTOR HAS GENERATRO AT 45KW?? 45 | | | OT 70??? | | | | | | I ONLY WANT TO SEE GENERATOR RISER, LOAD CALC, AND | | | SPECS FOR THE GENERATOR AND THE TRANSFER SWITCH. ALL | | | OTHER SHEETS ( THE ONES THE ARE DATED 7/15 AND STATE | | | ENTIRE SHEET REVISION) TAKEN OUT AND SUBMITTED | | | SEPARATELY FOR A REVISION. | | | | | | WHEN SUBMITTING THE REVISION PLEASE SPELL OUT WHAT HAS | | | BEEN DONE FOR THE REVISION OTHERWISE IT TAKES LONGER TO | | | REVIEW. ENTIRE SHEET REVISED WILL PROBALBLY FAIL. |
|