| Plan Review Notes For Permit 19050028 |
| Permit Number |
19050028 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2020-08-18 13:30:31 | GENERATOR | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected]. | | | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 | | | AMENDMENTS | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | THIS PERMIT IS FOR THE ROOFTOP GENERATOR FROM MASTER | | | PERMIT (160701) AND REVISION (18071460) | | | 1) PLEASE SHOW THE GENERATOR CONNECTION TO THE ROOFTOP | | | STAND ON THE SIGNED AND SEALED DRAWINGS. | | | 2) PLEASE PROVIDE SIGNED AND SEALED ROOFTOP SCREENING | | | DETAILS FROM AN ARCHITECT OR ENGINEER TO COMPLY WITH | | | THE WIND LOADS PER FBC 1609 (SHOW ALL ATTACHMENTS | | | (SIZE, TYPE AND LENGTH) TO BUILD IT AND TO FASTEN TO | | | THE ROOF STRUCTURE). | | | 3) DRAWING (E1.3) THE LOCATION OF THE GENERATOR IS NOT | | | THE SAME AS ALL OF THE OTHER DRAWINGS - PLEASE CLARIFY | | | THE LOCATION SHOULD BE THE SAME ON ALL OF THE DRAWINGS. | | | 4) DRAWINGS THAT ARE REVISIONS TO OTHER PERMIT NUMBERS | | | SHOULD BE REVISED UNDER A SEPERATE PERMIT NUMBER - NOT | | | AS PART OF THE GENERATOR PERMIT. | | | 5) WHAT ARE THE ORIGINAL PERMIT NUMBERS FOR DRAWINGS | | | (A-405R) AND (A-107R) ? | | | | | | |
|