2020-08-18 13:30:31GENERATOR
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 THIS PERMIT IS FOR THE ROOFTOP GENERATOR FROM MASTER
 PERMIT (160701) AND REVISION (18071460)
 1) PLEASE SHOW THE GENERATOR CONNECTION TO THE ROOFTOP
 STAND ON THE SIGNED AND SEALED DRAWINGS.
 2) PLEASE PROVIDE SIGNED AND SEALED ROOFTOP SCREENING
 DETAILS FROM AN ARCHITECT OR ENGINEER TO COMPLY WITH
 THE WIND LOADS PER FBC 1609 (SHOW ALL ATTACHMENTS
 (SIZE, TYPE AND LENGTH) TO BUILD IT AND TO FASTEN TO
 THE ROOF STRUCTURE).
 3) DRAWING (E1.3) THE LOCATION OF THE GENERATOR IS NOT
 THE SAME AS ALL OF THE OTHER DRAWINGS - PLEASE CLARIFY
 THE LOCATION SHOULD BE THE SAME ON ALL OF THE DRAWINGS.
 4) DRAWINGS THAT ARE REVISIONS TO OTHER PERMIT NUMBERS
 SHOULD BE REVISED UNDER A SEPERATE PERMIT NUMBER - NOT
 AS PART OF THE GENERATOR PERMIT.
 5) WHAT ARE THE ORIGINAL PERMIT NUMBERS FOR DRAWINGS
 (A-405R) AND (A-107R) ?
  
  