| Plan Review Notes For Permit 19050028 |
| Permit Number |
19050028 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-06-05 10:46:53 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) THERE ARE NO LOCATIONS INDICATIONS SUBMITTED. | | | | | | PLEASE PROVIDE THE LOCATION OF THIS GENERATOR INCLUDING | | | ALL DIMENSIONS TO BUILDINGS, WINDOWS AND DOORS. | | | | | | | | | 2) THERE ARE NO INDICATIONS IF THIS GENERATOR WILL BE | | | PROVIDING POWER TO ANY LIFE SAFEY EQUIPMENT OR SYSTEMS. | | | | | | PLEASE PROVIDE DETAILS. | | | | | | | | | 3) THERE ARE NO INDICATIONS OF COMPLIANCE WITH ANY FIRE | | | CODES. | | | | | | BASED ON # 2 ABOVE IT MAY NEED TO COMPLY WITH BOTH NFPA | | | 110 AND 37 AS WELL AS OTHER APPLICABLE FIRE CODES. | | | | | | PLEASE PROVIDE ZCODE COMPLIANCE NOTES | | | | | | | | | 4) THERE ARE NO FOUNDATION DETAILS. | | | | | | PLEASE PROVIDE DETAILS, INCLUDING LOCATION, DIMENSIONS, | | | TIE-DOWNS, ETC. | | | | | | | | | 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | | | | | | | | | | |
|