| Plan Review Notes For Permit 19050027 |
| Permit Number |
19050027 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-06-04 13:08:54 | PLUMBING 1ST REVIEW**DENIED** | | | | | | | | | 1-PROVIDE CLEAR FLOOR SPACE AS REQUIRED IN | | | FBC-ACC606.2, TURNING SPACE AS REQUIRED IN FBC-ACC 304, | | | AND ACCESSIBLE ROUTE FBC-ACC 404 ON THE A SHEET NEW | | | WORK FOR BOTH THE BREAK ROOM SINK AND CAF? SINK. BEING | | | THAT THESE ARE 2 DIFFERENT SINKS BOTH SHALL APPLY WITH | | | THE FLORIDA ACCESSIBILITY CODE. | | | | | | 2-PROVIDE SANITARY ISOMETRIC DRAWING. SHT. P 01 REFERS | | | UNDER KEY NOTE (NEW VENT LINE) BUT NO ISOMETRIC | | | PROVIDE. FBC 107.3.5 | | | | | | 3- PROVIDE DIMENSIONS OF DOORWAYS AND PATHWAYS SHOWING | | | MIN ACCESSIBLE PATH. FBC 107.3.5 | | | | | | | | | TIM HUNT | | | PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR | | | BUILDING DIVISION | | | CITY OF WEST PALM BEACH | | | 401 CLEMATIS STREET, 1ST FLOOR | | | WEST PALM BEACH, FL 33401 | | | 561-248-2703 | | | [email protected] | | | [email protected] |
|