| 2019-06-06 13:32:51 | BUILDING REVIEW COMMENTS |
| | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| | |
| | NOTE: ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | SEC. 801.3 FBC-EXISTING BUILDING. |
| | |
| | 1- LIFE SAFETY PLAN ON SHEET A-7: |
| | |
| | A) A SET OF DOUBLE DOORS IN THE CORRIDOR LEADING TO THE |
| | TWO EXITS WERE ELIMINATED TO ALLOW THE OPEN OFFICE |
| | #319. IT LOOKS LIKE THE COMMON PATH OF TRAVEL WILL |
| | EXCEED 100 FEET AS REQUIRED BY TABLE 1006.2.1 |
| | FBC-BUILDING. PROVIDE THE COMMON PATH OF TRAVEL |
| | DISTANCE FROM THE MOST REMOTE POINT OF THE LAST |
| | WORKSTATION ON THIS NEW OPEN OFFICE AREA #319 AND FROM |
| | THE MOST REMOTE POINT OF THE NEW FILES ROOM #320. |
| | |
| | B) PROVIDE ALSO THE OVERALL TRAVEL DISTANCE FROM THE |
| | MOST REMOTE POINT OF THE LAST WORKSTATION ON THIS NEW |
| | NEW OPEN OFFICE AREA #319. AND FROM THE MOST REMOTE |
| | POINT OF THE NEW FILES ROOM #320. TABLE 1017.2 |
| | FBC-BUILDING. |
| | |
| | C) SHOW ALL THE EXITS SIGNS AS REQUIRED BY SEC. 1013.1 |
| | FBC-BUILDING FOR THE NEW OFFICE LAYOUT. |
| | |
| | D) REVISE CODE SECTIONS AND TABLES CITED ON THE LIFE |
| | SAFETY SUMMARY (SUITE #350) CHART SHOWN BELOW THE LIFE |
| | SAFETY FLOOR PLAN. THEY DO NOT CORRESPOND TO THE TABLES |
| | AND SECTIONS OF FBC-6TH EDITION. |
| | |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | PLEASE, INSERT CORRECTED PAGES INTO THE SUBMITTAL AND |
| | REMOVE/VOID THE PREVIOUSLY REVIEWED SHEETS. |
| | PLEASE DON'T STAPLE OLD DRAWINGS/DOCUMENTS . SUBMIT OLD |
| | DRAWINGS/DOCUMENTS FOR REFERENCE. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |
| | [email protected] |