| Plan Review Notes For Permit 19050002 |
| Permit Number |
19050002 |
|
| Review Stop |
THRESHOLD |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-05-24 11:33:27 | ***CORRECTIONS*** | | | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | 553.79(5) 2016, THIS IS A THRESHOLD BUILDING. THE | | | FOLLOWING IS REQUIRED PRIOR TO COMMENCEMENT: | | | | | | 1. COMPLETE THE THRESHOLD / SPECIAL INSPECTOR AGREEMENT | | | OF UNDERSTANDING; THIS HAS BEEN SENT VIA EMAIL TO | | | CONTRACTOR. | | | | | | 2. PROVIDE RESUMES AND COPIES OF LICENSES FOR ALL | | | PROPOSED INSPECTORS. | | | | | | 3. ALL PLANS ARE TO INCLUDE THE THRESHOLD STATEMENT | | | REQUIRED BY FS553.79(7)(D). ALL PLANS FOR THE BUILDING | | | WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY THE | | | ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT | | | THAT, TO THE BEST OF THE ARCHITECT?S OR ENGINEER?S | | | KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE | | | APPLICABLE MINIMUM BUILDING CODES AND THE APPLICABLE | | | FIRESAFETY STANDARDS AS DETERMINED BY THE LOCAL | | | AUTHORITY IN ACCORDANCE WITH THIS CHAPTER 553 AND | | | CHAPTER 633. | | | |
|