| Plan Review Notes For Permit 19041536 |
| Permit Number |
19041536 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-05-08 16:23:28 | PLUMBING 1ST REVIEW**DENIED** | | | | | | 1) PERMIT APPLICATION UNDER DESCRIPTION OF WORK AS TUB | | | TO SHOWER CONVERSION. PLAN SHOWS THE WATER HEATER TO BE | | | RELOCATED FOR THE SHOWER. PLEASE CLARIFY WHERE IS THE | | | TUB? FBC 107.2.1 | | | | | | 2) PROVIDE DETAIL OF WATER HEATER ENCLOSURE. FBC | | | 107.2.1 | | | | | | 3) PROVIDE DIMENSION'S OF BATHROOM SHOWING DISTANCE'S | | | BETWEEN FIXTURES AND DIMENSION OF SHOWER. SHOWER SHALL | | | BE MIN 900 SQ INCHES. FBC-R P2705.1 #5, P2708.1 | | | | | | 4) PROVIDE SANITARY ISOMETRIC DRAWING. FBC 107.3.5 | | | | | | 5) ELC PLAN AND PERMIT REQUIRED FOR WATER HEATER | | | RELOCATION. FBC 105.1 | | | | | | TIM HUNT | | | PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR | | | CITY OF WEST PALM BEACH | | | 561-248-2703 | | | [email protected] | | | [email protected] | | | | | | |
|