Plan Review Notes
Plan Review Notes For Permit 19041536
Permit Number 19041536
Review Stop P
Sequence Number 1
Notes
Date Text
2019-05-08 16:23:28PLUMBING 1ST REVIEW**DENIED**
  
 1) PERMIT APPLICATION UNDER DESCRIPTION OF WORK AS TUB
 TO SHOWER CONVERSION. PLAN SHOWS THE WATER HEATER TO BE
 RELOCATED FOR THE SHOWER. PLEASE CLARIFY WHERE IS THE
 TUB? FBC 107.2.1
  
 2) PROVIDE DETAIL OF WATER HEATER ENCLOSURE. FBC
 107.2.1
  
 3) PROVIDE DIMENSION'S OF BATHROOM SHOWING DISTANCE'S
 BETWEEN FIXTURES AND DIMENSION OF SHOWER. SHOWER SHALL
 BE MIN 900 SQ INCHES. FBC-R P2705.1 #5, P2708.1
  
 4) PROVIDE SANITARY ISOMETRIC DRAWING. FBC 107.3.5
  
 5) ELC PLAN AND PERMIT REQUIRED FOR WATER HEATER
 RELOCATION. FBC 105.1
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR
 CITY OF WEST PALM BEACH
 561-248-2703
 [email protected]
 [email protected]
  
  