| Plan Review Notes For Permit 19041534 |
| Permit Number |
19041534 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-05-20 14:32:03 | PLUMBING 1ST REVISION REVIEW**DENIED** | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | 1) YOU CALL OUT ALL RESTROOMS AS UNISEX. THE ONLY | | | RESTROOM PERMITTED TO BE UNISEX IS THE WAREHOUSE | | | RESTROOM AS THE OCCUPANT LOAD IS UNDER 16 PER 403.2. | | | LABEL EACH OF THE OTHER RESTROOM'S AS MEN'S OR WOMENS. | | | | | | 2) RESTROOM # 108 WAS REDLINE PROVISO ON APPROVED PLAN | | | MUST COMPLY WITH ADA. THIS REVISION IS ONLY CALLING FOR | | | GRAB BAR REINFORCEMENT IS STILL SHOWING TOO SMALL @ 7' | | | TO MEET MIN ADA. PROVIDE CLEAR FLOOR SPACE, TURNING | | | SPACE, CHANGE DOOR SO NOT TO SWING INTO THE SINKS CLEAR | | | FLOOR SPACE. FBC-ACC 604.3, 603.2.1, 603.2.3 | | | | | | 3) SHOW RESTROOMS 106 AND 107 CLEAR FLOOR SPACE AND | | | TURNING SPACE. FBC-ACC 604.3, 603.2.1 | | | | | | TIM HUNT | | | PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR | | | BUILDING DIVISION | | | CITY OF WEST PALM BEACH | | | 401 CLEMATIS STREET, 1ST FLOOR | | | WEST PALM BEACH, FL 33401 | | | 561-248-2703 | | | [email protected] | | | [email protected] | | | |
|