Plan Review Notes
Plan Review Notes For Permit 19041488
Permit Number 19041488
Review Stop G
Sequence Number 4
Notes
Date Text
2019-07-08 11:42:071) THE SUBMITTED GAS PLAN DOES NOT SHOW THE TOTAL BTU
 LOAD ON THIS SYSTEM PER CITY RECORDS. THE FOLLOWING GAS
 APPLIANCES ARE ALSO CONNECTED TO THIS SYSTEM AND MUST
 BE INCLUDED ON THE RISER DIAGRAM:
 A) FIREPLACE - 40,000 BTU'S
 B) STOVE - 60,000 BTU'S
 C) WATER HEATER - 35,000 BTU'S
 D) FIRE TABLE - 50,000 BTU'S
 TOTAL - 185,000 BTU'S
 2) THE POOL HEATER SHALL HAVE A THERMAL EFFICIENCY OF
 82% PER THE 2017 FBC-ENERGY SEC.R403.10.4. SUBMIT
 DOCUMENTAION.
 3) A VAPOR -RETARDANT POOL COVER OR A LIQUID COVER IS
 REQUIRED ON OR AT THE WATER SURFACE PER 2017 FBC-ENERGY
 SEC. R 403.10.3.
 4) THE GAS DRAWING REFERS TO ITRON REGULATORS. ARE THE
 EXISTING REGULATORS BEING REPLACED? IF SO, SUBMIT
 INSTALLATION INSTRUCTIONS AND MANUF. SPECIFICATIONS FOR
 THE REGULATORS. REGULATORS SHALL BE APPROVED FOR
 EXTERIOR USE. , 2017 FBC-RES. SEC. G2421.1.
 5) WHY IS THE GENERATOR BEING REMOVED IF THE PERMIT IS
 FOR A POOL? CLARIFY ON THE PLANS. WPB AMEND. TO FBC
 SEC. 107.2.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  