Plan Review Notes
Plan Review Notes For Permit 19041488
Permit Number 19041488
Review Stop P
Sequence Number 2
Notes
Date Text
2019-06-19 16:48:33PLUMBING 2ND REVIEW**DENIED**
  
 1) THE SUBMITTED TDH CALCULATIONS DO NOT APPEAR TO SHOW
 THE FRICTION LOSS THROUGH ALL THE SYSTEM COMPONENTS.
 THE CALCULATOR SHOWS THE PIPE, FITTINGS, VALVES,
 HEATER, FILTER, ETC. BUT THERE IS NO FRICTION LOSS
 ASSOCIATED WITH THESE ITEMS. CLARIFY. FBC 107.2.1
  
 2) ALL NEW SUBMITTED SHEETS THAT BEAR R.GLORSKI
 PROFESSIONAL ENGINEER ARE REQUIRED TO BE WET SIGNED.
 COPIES ARE NOT PERMITTED. F.S 471
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR