| Plan Review Notes For Permit 19041488 |
| Permit Number |
19041488 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2019-06-19 16:48:33 | PLUMBING 2ND REVIEW**DENIED** | | | | | | 1) THE SUBMITTED TDH CALCULATIONS DO NOT APPEAR TO SHOW | | | THE FRICTION LOSS THROUGH ALL THE SYSTEM COMPONENTS. | | | THE CALCULATOR SHOWS THE PIPE, FITTINGS, VALVES, | | | HEATER, FILTER, ETC. BUT THERE IS NO FRICTION LOSS | | | ASSOCIATED WITH THESE ITEMS. CLARIFY. FBC 107.2.1 | | | | | | 2) ALL NEW SUBMITTED SHEETS THAT BEAR R.GLORSKI | | | PROFESSIONAL ENGINEER ARE REQUIRED TO BE WET SIGNED. | | | COPIES ARE NOT PERMITTED. F.S 471 | | | | | | TIM HUNT | | | PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR | | | BUILDING DIVISION | | | CITY OF WEST PALM BEACH | | | 401 CLEMATIS STREET, 1ST FLOOR | | | WEST PALM BEACH, FL 33401 | | | 561-248-2703 | | | [email protected] | | | [email protected] |
|