| 2019-05-07 11:58:42 | PLUMBING 1ST REVIEW**DENIED** | | | | | | | | | 1) SUBMIT TOTAL DYNAMIC HEAD CALCULATIONS FOR THE | | | MAXIMUM SYSTEM FLOW. THE MAXIMUM FLOW OF THE PUMP FROM | | | ITS PUMP CURVE AND THE SIMPLIFIED TOTAL DYNAMIC HEAD | | | CALCULATION IS NO LONGER ALLOWED TO BE USED IN | | | DETERMINING MAXIMUM SYSTEM FLOW RATE PER ANSI/APSP/ICC | | | 7 - 2013 SECS. 4.4.9, 4.4.9.1. THE 2013 EDITION | | | ADDRESSES FLOW RATE IN GALLONS PER MINUTE (GPM). IT | | | REQUIRES THAT MAXIMUM SYSTEM FLOW RATE DOES NOT EXCEED | | | THE LISTED MAXIMUM FLOW RATE OF THE SUCTION OUTLET | | | FITTING ASSEMBLY (DRAIN COVER).THE TDH CALCULATIONS | | | MUST INCLUDE ALL OF THE SYSTEM COMPONENTS INCLUDING | | | SUCTION AND RETURN PIPING, FITTINGS, VALVES, HEATER, | | | FILTER, AND CHLORINATOR. ALL SYSTEM COMPONENTS EXCEPT | | | THE PUMP. | | | | | | 2) PROVIDE WHICH GAS POOL HEATER YOU ARE USING AND | | | SUBMIT THE COMPLETE INSTALLATION MANUAL. PROPOSAL CALLS | | | OUT FOR A 335,000 BTU HEATER, SHT #2 LIST HEATER AS | | | 400,00 BTU WHILE SHT #5 CALLS OUT 350,00 BTU. PLEASE | | | CLARIFY. FBC 107.2.1 | | | | | | 3) ADD NOTE THAT A VAPOR-RETARDANT COVER TO LIMIT HEAT | | | LOSS IS REQUIRED. 2017 FBC- ENERGY- SEC. R 403.10.3. | | | | | | | | | TIM HUNT | | | PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR | | | BUILDING DIVISION | | | CITY OF WEST PALM BEACH | | | 401 CLEMATIS STREET, 1ST FLOOR | | | WEST PALM BEACH, FL 33401 | | | 561-248-2703 | | | [email protected] | | | [email protected] | | | | | | | | | | | | |
|