2019-05-07 11:58:42PLUMBING 1ST REVIEW**DENIED**
  
  
 1) SUBMIT TOTAL DYNAMIC HEAD CALCULATIONS FOR THE
 MAXIMUM SYSTEM FLOW. THE MAXIMUM FLOW OF THE PUMP FROM
 ITS PUMP CURVE AND THE SIMPLIFIED TOTAL DYNAMIC HEAD
 CALCULATION IS NO LONGER ALLOWED TO BE USED IN
 DETERMINING MAXIMUM SYSTEM FLOW RATE PER ANSI/APSP/ICC
 7 - 2013 SECS. 4.4.9, 4.4.9.1. THE 2013 EDITION
 ADDRESSES FLOW RATE IN GALLONS PER MINUTE (GPM). IT
 REQUIRES THAT MAXIMUM SYSTEM FLOW RATE DOES NOT EXCEED
 THE LISTED MAXIMUM FLOW RATE OF THE SUCTION OUTLET
 FITTING ASSEMBLY (DRAIN COVER).THE TDH CALCULATIONS
 MUST INCLUDE ALL OF THE SYSTEM COMPONENTS INCLUDING
 SUCTION AND RETURN PIPING, FITTINGS, VALVES, HEATER,
 FILTER, AND CHLORINATOR. ALL SYSTEM COMPONENTS EXCEPT
 THE PUMP.
  
 2) PROVIDE WHICH GAS POOL HEATER YOU ARE USING AND
 SUBMIT THE COMPLETE INSTALLATION MANUAL. PROPOSAL CALLS
 OUT FOR A 335,000 BTU HEATER, SHT #2 LIST HEATER AS
 400,00 BTU WHILE SHT #5 CALLS OUT 350,00 BTU. PLEASE
 CLARIFY. FBC 107.2.1
  
 3) ADD NOTE THAT A VAPOR-RETARDANT COVER TO LIMIT HEAT
 LOSS IS REQUIRED. 2017 FBC- ENERGY- SEC. R 403.10.3.
  
  