| Plan Review Notes For Permit 19041487 |
| Permit Number |
19041487 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2019-08-15 10:42:02 | 1) THERE ARE TWO DIFFERENT SETS OF PLANS IN THIS | | | SUBMITTAL PACKAGE. ONE SET IS FROM FARMER & IRWIN AND | | | THE OTHER IS FROM GENERAL PLUMBING. REMOVE ALL OLD | | | PLANS AND DOCUMENTS FROM THIS SUBMITTAL AND SUBMIT TWO | | | COPIES OF THE PLANS TO BE USED. WPB AMEND. TO FBC SEC. | | | 107.2.1. | | | 2) THE WATER RISER SUBMITTED FROM GENERAL PLUMBING | | | DIFFICULT TO SEE SOME OF THE PIPE SIZE. SUBMIT TWO | | | COPIES OF AN EXPANDED LEGIBLE PLAN FOR REVIEW. WPB | | | AMEND. TO FBC SEC. 107.2.1. | | | 3) SUBMIT MANUFACTURER'S INSTALLATION INSTRUCTIONS FOR | | | THE PEX PIPE.2017 FBC-PLUMBING SEC. 303.2. | | | 4) HOW WILL THE PIPING BE PROTECTED FROM UV RAYS? | | | SUBMIT INFORMATION ON THE PLANS. WPB AMEND. TO FBC SEC. | | | 107.2.1. | | | 5) ONE SPECIFICATION SHEET THAT WAS SUBMITTED WHICH HAS | | | SEVERAL SPECIFICATIONS ON IT IS ILLEGIBLE.WPB AMEND. TO | | | FBC SEC. 107.2.1. | | | 6) SUBMIT DOCUMENTATION THAT THE JM EAGLE FITTINGS ARE | | | COMPATIBLE WITH THE PEX PIPING. | | | 7) TWO DIFFERENT SPECIFICATIONS HAVE BEEN SUBMITTTED | | | FOR THE CLAMPS. WHICH ONES ARE BEING USED? CLARIFY. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | |
|