| Plan Review Notes For Permit 19041487 |
| Permit Number |
19041487 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-05-02 10:25:53 | PLUMBING 1ST REVIEW**DENIED**NOTE - A STOP WORK ORDER | | | WAS ISSUED FOR WORK STARTING BEFORE ISSUANCE OF PERMIT. | | | A 4X PERMIT FEE HAS BEEN APPLIED TO THIS PERMIT. IF YOU | | | WISH TO DISCUSS THE MATTER PLEASE CONTACT TIM LARGE | | | CHIEF PLUMBING INSPECTOR @ 561-805-6692 | | | | | | 1) PIPING SHALL NOT BE INSTALLED WITH IN 5' OF U.V | | | LIGHT. PER NOTES FROM THE FIELD INSPECTOR ALL PIPING IS | | | INSTALLED IN DIRECT SUNLIGHT. PER THE MANUFACTURES | | | INSTALLATION MANUAL 22.11.16 SECTION 3.2 (C) #2 | | | | | | 2) STRAPPING MATERIAL CALLED OUT ON PLAN IS NOT AN | | | APPROVED METHOD AND MAY CUT INTO THE PIPING MATERIAL. | | | PER THE MANUFACTURES INSTALLATION MANUAL 22.11.16 2.2 | | | (D) #2 | | | | | | 3) PROPOSAL INCLUSIONS # 3 CALLS OUT FOR WATER HEATER | | | AS SPECIFIED. THERE IS NOT WATER HEATER OR HOT WATER | | | PIPING SHOWN ON THE PLAN. PLEASE CLARIFY FBC 107.2.1. | | | | | | 4) PIPING SHOWN ON PLAN APPEARS TO BE TIGHT AND | | | STRAPPING METHOD WOULD NOT ALLOW FOR PROPER EXPANSION. | | | PER THE MANUFACTURES INSTALLATION MANUAL | | | | | | 5) PLANS SUBMITTED MUST BE SIGNED BY THE PERSON WHO | | | DESIGNED THEM TAKING RESPONSIBILITY. F.A.C 471, 781, | | | 489 | | | | | | | | | TIM HUNT | | | PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR | | | BUILDING DIVISION | | | CITY OF WEST PALM BEACH | | | 401 CLEMATIS STREET, 1ST FLOOR | | | WEST PALM BEACH, FL 33401 | | | 561-248-2703 | | | [email protected] | | | [email protected] |
|