| 2019-05-01 15:53:37 | BUILDING PLAN REVIEW | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | | | | JOSEAN A. DUPREY E.I., BN, PX | | | BUILDING PLANS EXAMINER | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6716 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | 1ST REVIEW | | | RESULTS: DENIED | | | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED | | | BELOW. | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1. THE APPENDIX SHEET INDICATE THE APPENDIX F IS FOR | | | TENSION TEST PROCEDURE AND LOADING SCHEDULE, HOWEVER | | | THIS TEST PROCEDURE WAS NOT INCLUDED IN THE PACKAGE. | | | THE APPENDIX F INCLUDED IS FOR LATERAL TEST AND NO | | | APPENDIX G IS ON THE PACKAGE. PLEASE CLARIFY IF THE | | | TENSION TEST IS GOING TO BE PERFORM. FBC 107 |
|