| 2021-06-15 06:37:25 | 1) THE GAS DRAWING SHOWS THE 2 PSI LINE GOING TO THE |
| | EXISTING KITCHEN. HOW WILL THE EXISTING APPLIANCES BE |
| | PROTECTED FROM OVERPRESSURE? WILL EACH APPLIANCE BE |
| | PROTECTED WITH A REGULATOR OR WILL ONE REGULATOR BE |
| | INSTALLED ON THE LINE TO THE KITCHEN? CLEARLY SHOW ON |
| | THE PLANAS TO WHAT WILL BE DONE. |
| | 2) A LISTED SHUTOFF VALVE SHALL BE INSTALLED |
| | IMMEDIATELY AHEAD OF EACH REGULATOR. FBC-FUEL GAS |
| | SEC.409.4. |
| | 3) WHERE CONNECTED TO RIGID PIPING, A UNION SHALL BE |
| | INSTALLED WITHIN 1 FOOT OF EITHER SIDE OF THE MP |
| | REGULATOR. FBC-FUEL GAS SEC. 410.2 (7).2ND REQUEST. |
| | 4) A REGULATOR, SHUTOFF VALVE AND UNION IS REQUIRED AT |
| | THE BOILER.FBC-FUEL GAS SEC.409.4, FBC-FUEL GAS SEC. |
| | 410.2 (7), 410.1. |
| | 5) SUBMIT A PIPING DETAIL FOR THE PIPING AT THE |
| | GENERATORS.WPB AMEND. TO FBC SEC. 107.2.1. |
| | 6) SUBMIT MANUFACTURER'S SPECIFICATIONS AND |
| | INSTALLATION INSTRUCTIONS FOR THE PRESSURE |
| | REGULATORS.REGULATORS SHALL BE APPROVED FOR OUTDOOR |
| | USE. FBC-FUEL GAS SEC. 410.1.2ND REQUEST. |
| | 7) SHOW THE DISTANCE FROM THE REGULATORS TOTHE FURTHEST |
| | OUTLET ON THE LOW PRESSURE SIDE OF EACH REGULAOR. THIS |
| | IS REQUIRED TO ENSURE CORRECT SIZING OF THE EXISTING |
| | SYSTEM. FBC-FUEL GAS SEC.401.3, 401.4.401.8. |
| | 8) IDENTIFY ON THE REGULATOR SPECIFICATIONS WHICH |
| | REGULATOR MODEL IS BEING INSTALLED.THE REGULATOR SHALL |
| | BE CAPABLE OF HANDLING THE BTU LOAD OF THE APPLIANCE OR |
| | THE EQUIPMENT. 2017 FBC-FUEL GAS SEC.410.2 (3). 2ND |
| | REQUEST. |
| | 9) IDENTIFY EACH APPLIANCE IN THE KITCHEN AND THE |
| | CORRESPONDING BTU LOAD. WPB AMEND. TO FBC SEC. 107.2.1. |
| | 10) PLACE THE ENTIRE BTU LOAD OF THE SYSTEM ON THE |
| | PLANS. |
| | |