| Date |
Text |
| 2019-07-26 11:27:19 | ***PLEASE NOTE SOILS REPORT SIGNATURE RECEIVED |
| | 07/26/2019 AND VERIFIED AS CONSISTANT WITH UPLOADED |
| | VERSION. S/S IS GOOD. ON FILE WITH APPLICATION IN |
| | LIBRARY.*** |
| 2019-07-24 11:22:01 | BUILDING PLAN REVIEW - SIGNATURE AND SEAL |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | BUILDING PLANS EXAMINER, PX3169 |
| | 1&2 FAMILY PLANS EXAMINER, SFP306 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | 2ND REVIEW |
| | |
| | RESULTS: DENIED |
| | |
| | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| | BELOW. |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | 1. CANNOT VERIFY ENGINEER'S SIGNATURE ON SOILS REPORT. |
| | REVIEW RESPONSE INDICATES A HARD COPY HAS BEEN |
| | PROVIDED. CANNOT LOCATE THIS HARD COPY. PROVIDE A HARD |
| | COPY OF THE SOILS REPORT WITH ORIGINAL SIGNATURE AND |
| | SEAL OF ENGINEER AT TIME OF PERMIT PICK-UP. |
| | |
| | 2. MECHANICAL, ELECTRICAL AND PLUMBING PLANS REQUIRE |
| | EITHER A SIGNATURE FROM A CONTRACTOR OR SIGNATURE AND |
| | SEAL OF A DESIGN PROFESSIONAL. |
| | FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS |
| | AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE |
| | OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO |
| | SECTION 107.3.5) AND F.S. 481.229. |
| | |
| | 3. PLAN PAGES A-1, S-1 & S-2 HAVE BEEN SIGNED AND |
| | SEALED BY A LICENSED PROFESSIONAL ENGINEER. THIS |
| | SIGNATURE AND SEAL HAS BEEN SELF CERTIFIED BY THE |
| | ENGINEER. PER FS 668.003, PROFESSIONAL ENGINEER'S |
| | CANNOT SELF CERTIFIY THEIR SIGNATURE AND SEAL. |
| | PLEASE ACCEPT THIS AS NOTICE THAT THE BUILDING OFFICIAL |
| | HAS DECIDED TO ACCEPT THE ENGINEER'S SELF CERTIFIED |
| | SIGNATURE AND SEAL ON A ONE TIME BASIS. ENGINEER SHALL |
| | EMPLOY THE SERVICES OF A THIRD PARTY ENTITY TO CERTIFY |
| | THEIR SIGNATURE AND SEAL. |
| | |
| | FLORIDA PROFESSIONAL ENGINEERS MAY NOT SELF CERTIFY |
| | DIGITAL SIGATURES AND SEALS PER FS 668.003. |
| | |
| 2019-07-09 14:17:38 | REGARDING PLUMBING, DIGITAL SIGNATURE IS NOT ISSUED IN |
| | A MANNER WHICH IS ACCEPTABLE TO EITHER FBPE OR FLORIDA |
| | BOARD OF PROFESSIONAL ENGINEERS. THIS TYPE OF SELF |
| | CERTIFICATION IS NOT INTENDED TO BE USED FOR |
| | PROFESSIONAL PURPOSES. THIRD PARTY CERTIFICATION IS |
| | REQUIRED. |