2019-05-13 10:41:48PLUMBING 1ST REVIEW**DENIED**
  
 1) PROVIDE LOCATION OF ACCESSIBLE SHUT OFF VALVES FOR
 THE STACK WASHER AND DRYER. FBC-RES P2903.9.3
  
 2) DISHWASHER SHALL NOT DIRECTLY CONNECT INTO THE
 SANITARY DRAINAGE SYSTEM. THE DISHWASHER DISCHARGE PIPE
 OR TUBING SHALL RISE TO THE UNDERSIDE OF THE COUNTER
 AND BE FASTENED OR OTHERWISE HELD IN THAT POSITION
 BEFORE CONNECTING TO THE HEAD OF THE FOOD-WASTE
 DISPOSER OR TO A WYE FITTING IN THE SINK TAILPIECE.
 FBC-RES P2717.2. APPROVED DIRECTIONAL-TYPE BRANCH
 FITTINGS SHALL BE INSTALLED IN FIXTURE TAILPIECES
 RECEIVING THE DISCHARGE FROM FOOD-WASTE DISPOSER UNITS
 OR DISHWASHERS.FBC-RES P2707.1
  
 3) PROVIDE NOTE ON PLANS THAT TUB/ SHOWER VALVES SHALL
 BE ASSE 1016 APPROVED. FBC-RES P 2708.4
  
 4) PROVIDE SHOWER PAN DETAIL. FBC-RES P2709.3
  
 5) PROVIDEWATER HEATER DISCHARGE DETAIL SHOWING RELIEF
 DISCHARGING INTO PAN. FBC-RES P2804.6.1 (5) AND PAN
 DRAIN WILL DISCHARGE TO THE OUTSIDE MIN 6" ABOVE GROUND
 SURFACE. FBC-RES P2801.6.2
  
 6) PROVIDE NOTE THAT ALL HOT WATER PIPING SHALL BE
 INSULATED MIN R-3 VALUE. FBC-ENERGY R403.5.3
  
 7) MIN E.F RATING OF WATER HEATER SHALL BE .97. YOUR
 R405-2017 FORM CALLS OUT ONLY .95. MOST MANUFACTURES
 HAVE GONE TO THE NEW UEF RATING SYSTEM WHICH THE MIN IS
 .92 UEF. FBC-ENERGY R403.5.6.2, C404.2.
  
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR
 CITY OF WEST PALM BEACH
 561-248-2703
 [email protected]
 [email protected]