| 2019-05-13 10:41:48 | PLUMBING 1ST REVIEW**DENIED** |
| | |
| | 1) PROVIDE LOCATION OF ACCESSIBLE SHUT OFF VALVES FOR |
| | THE STACK WASHER AND DRYER. FBC-RES P2903.9.3 |
| | |
| | 2) DISHWASHER SHALL NOT DIRECTLY CONNECT INTO THE |
| | SANITARY DRAINAGE SYSTEM. THE DISHWASHER DISCHARGE PIPE |
| | OR TUBING SHALL RISE TO THE UNDERSIDE OF THE COUNTER |
| | AND BE FASTENED OR OTHERWISE HELD IN THAT POSITION |
| | BEFORE CONNECTING TO THE HEAD OF THE FOOD-WASTE |
| | DISPOSER OR TO A WYE FITTING IN THE SINK TAILPIECE. |
| | FBC-RES P2717.2. APPROVED DIRECTIONAL-TYPE BRANCH |
| | FITTINGS SHALL BE INSTALLED IN FIXTURE TAILPIECES |
| | RECEIVING THE DISCHARGE FROM FOOD-WASTE DISPOSER UNITS |
| | OR DISHWASHERS.FBC-RES P2707.1 |
| | |
| | 3) PROVIDE NOTE ON PLANS THAT TUB/ SHOWER VALVES SHALL |
| | BE ASSE 1016 APPROVED. FBC-RES P 2708.4 |
| | |
| | 4) PROVIDE SHOWER PAN DETAIL. FBC-RES P2709.3 |
| | |
| | 5) PROVIDEWATER HEATER DISCHARGE DETAIL SHOWING RELIEF |
| | DISCHARGING INTO PAN. FBC-RES P2804.6.1 (5) AND PAN |
| | DRAIN WILL DISCHARGE TO THE OUTSIDE MIN 6" ABOVE GROUND |
| | SURFACE. FBC-RES P2801.6.2 |
| | |
| | 6) PROVIDE NOTE THAT ALL HOT WATER PIPING SHALL BE |
| | INSULATED MIN R-3 VALUE. FBC-ENERGY R403.5.3 |
| | |
| | 7) MIN E.F RATING OF WATER HEATER SHALL BE .97. YOUR |
| | R405-2017 FORM CALLS OUT ONLY .95. MOST MANUFACTURES |
| | HAVE GONE TO THE NEW UEF RATING SYSTEM WHICH THE MIN IS |
| | .92 UEF. FBC-ENERGY R403.5.6.2, C404.2. |
| | |
| | |
| | TIM HUNT |
| | PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR |
| | CITY OF WEST PALM BEACH |
| | 561-248-2703 |