| Date |
Text |
| 2019-05-13 15:26:59 | MECHANICAL PLAN REVIEW |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | BUILDING PLANS EXAMINER, PX3169 |
| | 1&2 FAMILY PLANS EXAMINER, SFP306 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | 1ST REVIEW |
| | RESULTS: DENIED |
| | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| | BELOW. |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | 1. PROVIDE COPY OF MIAMI DADE NOA 15-0903.08 FOR |
| | EQUIPMENT TIE DOWN. |
| | |
| | 2. PROVIDE DETAIL OF AH CONDENSATE DISPOSAL LINE. |
| | PROVIDE A CONDENSATE DISPOSAL PLAN- FBC R M1411.3 |
| | M1411.3 CONDENSATE DISPOSAL. |
| | CONDENSATE FROM COOLING COILS AND EVAPORATORS SHALL BE |
| | CONVEYED FROM THE DRAIN PAN OUTLET TO AN APPROVED PLACE |
| | OF DISPOSAL. SUCH PIPING SHALL MAINTAIN A MINIMUM |
| | HORIZONTAL SLOPE IN THE DIRECTION OF DISCHARGE OF NOT |
| | LESS THAN 1/8 UNIT VERTICAL IN 12 UNITS HORIZONTAL |
| | (1-PERCENT SLOPE). CONDENSATE SHALL NOT DISCHARGE INTO |
| | A STREET, ALLEY OR OTHER AREAS WHERE IT WOULD CAUSE A |
| | NUISANCE. |
| | |
| | 3. PROVIDE DETAIL OF BATHROOM EXHAUST DUCTS. |
| | M1506.3 EXHAUST OPENINGS. |
| | AIR EXHAUST OPENINGS SHALL TERMINATE NOT LESS THAN 3 |
| | FEET (914 MM) FROM PROPERTY LINES; 3 FEET (914 MM) FROM |
| | OPERABLE AND NON OPERABLE OPENINGS INTO THE BUILDING |
| | AND 10 FEET (3048 MM) FROM MECHANICAL AIR INTAKES |
| | EXCEPT WHERE THE OPENING IS LOCATED 3 FEET (914 MM) |
| | ABOVE THE AIR INTAKE. OPENINGS SHALL COMPLY WITH |
| | SECTIONS R303.5.2 AND R303.6. |
| | |
| | 4. PROVIDE LOCKING PORT CAPS AT EXTERIOR CU. |
| | M1411.8 LOCKING ACCESS PORT CAPS. |
| | REFRIGERANT CIRCUIT ACCESS PORTS LOCATED OUTDOORS SHALL |
| | BE FITTED WITH LOCKING-TYPE TAMPER-RESISTANT CAPS OR |
| | SHALL BE OTHERWISE SECURED TO PREVENT UNAUTHORIZED |
| | ACCESS. |
| | EXCEPTION: NO LOCKING-TYPE TAMPER-RESISTANT CAPS ARE |
| | REQUIRED IF PORTS ARE LOCATED INSIDE THE CONDENSING |
| | UNIT CABINET. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY |
| | REVIEWED SHEETS DETACHED. |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |