| 2019-05-28 19:33:42 | 3RD REVIEW: |
| | 2017 FLORIDA BUILDING CODE 6TH EDITION |
| | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| | EDITION |
| | |
| | PLUMBING COMMENTS: IN ORDER TO GET THE GAS PLAN |
| | APPROVED I SUGGEST A MEETING PLEASE CONNECT ME TO SET |
| | UP TIME AND DATE SEE INFO BELOW. |
| | |
| | 1. THE PLAN SHEETS SHALL MATCH SHT. P-1 SHOWS PE |
| | UNDERGROUND GAS PIPING SHT. G-1 SHOWS A DIFFERENT TYPE |
| | OF PIPING GMP IT ALSO DOES NOT SHOW FUTURE BBQ, THE |
| | WATER HEATER IS NOT SHOWN IN SAME LOCATION. PLEASE |
| | CLARIFY. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 2. SHT G-1 LIST THE SYSTEM AS LP GAS IS THIS CORRECT IF |
| | SO SHOW LOCATION OF LP TANK AND NOTE A SEPARATE PERMIT |
| | IS REQUIRED FOR THE LP TANK. PLEASE CLARIFY. PER WPB |
| | AMEND TO FBC 107.2.1 |
| | |
| | 3. PLEASE PROVIDE AN ABBREVIATION LEGEND I DO NOT |
| | RECOGNIZE THESE GMP, IHWH, MBTUH, FUT. PLEASE CLARIFY. |
| | PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 4. PLEASE CLARIFY ON PLAN IF PIPING IS RUNNING UNDER |
| | GROUND, GALVANIZED SHALL NOT BE BURIED DIRECTLY UNDER |
| | GROUND IT SHALL BE SLEEVED SHOW SLEEVE DETAIL ON PLAN. |
| | PER FBC RES G2415.11, G2415.11.1 |
| | |
| | 5. NOTE ON THE PLANPLUMBING AND GAS SHALL COMPLY WITH |
| | FLORIDA BUILDING CODE RESIDENTIAL 2017 6TH EDITION |
| | |
| | 6. 2ND REQUEST SUBMIT TWO COPIES OF THE MANUFACTURER?S |
| | SPECIFICATION SHEETS / INSTALLATION MANUAL FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54, |
| | NFPA 58, AND FBC-2017 FUEL GAS CODE SEC. 402.2, AND |
| | 301.3 OR 2017 FBC-RES. SEC. G2404.3. GAS APPLIANCES |
| | SHALL BE LISTED AND LABELED. THE INSTALLATION MANUALS |
| | FOR ALL GAS APPLIANCES / EQUIPMENT SHALL BE ONSITE AT |
| | THE TIME OF INSPECTION. FGC SEC.305.1, FBC-RES. |
| | SEC.G2408.1. |
| | |
| | 7. 2ND REQUEST SHOW TANKLESS HEATER MOUNTED A MIN OF |
| | 4FT FROM OPERABLE OPENING IN BUILDING. PER WPB AMEND TO |
| | FBC 107.2.1 |
| | |
| | 8. A DRIP LEG IS REQUIRED AT EACH APPLIANCES PLEASE |
| | SHOW ON PLAN. PER FBC RES G2419.4 |
| | |
| | |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |