Plan Review Notes
Plan Review Notes For Permit 19041340
Permit Number 19041340
Review Stop G
Sequence Number 1
Notes
Date Text
2019-04-30 16:20:02GAS 1ST REVISION REVIEW**DENIED** NONE OF THE PLANS
 PROVIDE HAVE BEEN SIGN AND SEALED AS REQUIRED BY THE
 DESIGN PROFESSIONAL. 61G1-16.001 ARCHITECT?S AND
 INTERIOR DESIGNER?S SEAL. EACH ARCHITECT AND INTERIOR
 DESIGNER SHALL ACQUIRE A SEAL WITH WHICH SHE OR HE
 SHALL IDENTIFY ALL PLANS, SPECIFICATIONS OR REPORTS
 PREPARED OR ISSUED BY HER OR HIM AND FILED FOR PUBLIC
 RECORD. THE SEAL SHALL BE CAPABLE OF LEAVING A
 PERMANENT INK REPRESENTATION OR OTHER FORM OF EMBOSSING
 OR OPAQUE AND PERMANENT IMPRESSION, WHICH ALSO MAY BE
 COMPUTER GENERATED IMPRESSIONS, ON THE SURFACE OF
 PRINTS OR OTHER DUPLICATIONS OF DRAWINGS, AND, AS
 APPROPRIATE, UPON SPECIFICATION PAGES, AND OTHER
 ARTICLES OF SERVICE.
  
  
 A CHANGE IN THE VALUE OF WORK NEEDS TO BE ADJUSTED FOR
 THE REVISION CHANGES.
  
 1) A PARTIAL GAS PLAN HAS BEEN SUBMITTED WITH OUT A GAS
 PERMIT AGAIN. GAS PERMIT IS REQUIRED AND THE FOLLOWING
 COMMENTS BELOW NEED TO BE ADDRESSED. FBC 105.1
  
 2) SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE
 LENGTH OF ALL CUT SECTIONS OF PIPE PER 2017 FBC-FUEL
 GAS, SECS. 402.4.1, 402.4.2. OR 2017 FBC-RES SEC.
 G2413.4.1, G2413.4.2.
  
 3) SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE
 CORRUGATED STAINLESS STEEL TUBING (IF APPLICABLE) FOR
 EACH PIPE SIZE. WPB AMENDMENTS TO FBC SEC.107.2.1.
  
 4) LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL
 BTU LOAD ON THE SYSTEM. REFER TO THE 2017 FBC-FUEL GAS
 SECS.401.8, 402.2, AND TABLES 402.4 (1) THRU 402.4 (37)
 OR 2017 FBC-RES. SEC. G2413.3, G2413.4 AND TABLES
 G2413.4 (1 ) THROUGH G2413.4 (21).
  
 5) SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS
 METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND / OR SYSTEM PER THE 2017
 FBC-FUEL GAS SEC.402.4.1, 402.4.2, OR 2017 FBC-RES.
 SEC. G 2413.4.1, G2413.4.2
  
 6) SUBMIT COMBUSTION AIR CALCULATIONS FOR THE RANGE/
 STOVE. WHERE COMBUSTION AIR IS PROVIDED BY THE
 BUILDING?S MECHANICAL VENTILATION SYSTEM, THE SYSTEM
 SHALL PROVIDE THE SPECIFIED COMBUSTION AIR RATE IN
 ADDITION TO THE REQUIRED VENTILATION AIR. 2017 FBC-FUEL
 GAS SEC.304.9.3 OR FBCR G2407.9.3.
  
 7) SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES
 USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE
 PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM
 THE GAS CODE OR OTHER STANDARD THAT WERE USED IN THE
 DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017 FBC-FUEL
 GAS SECS. 401.4, 401.8, 402.3, AND TABLES 402.4 (1)
 THRU 402.4 (37) OR 2017 FBC-RES. SEC. G2413.3, G2412.8,
 G2413.1, G2413.2, & G2413.3.
  
 8) SUBMIT TWO COPIES OF A HOUSE PLAN SHOWING THE
 LOCATION OF THE TANKLESS WATER HEATER AND THE LOCATION
 AND DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN
 RELATION TO THE WATER HEATER. THE LOCATION OF THE WATER
 HEATER SHALL COMPLY WITH THE MANUFACTURER'S
 INSTALLATION INSTRUCTIONS. THE HOUSE PLAN CAN BE HAND
 DRAWN. WPB AMEND. TO FBC SEC. 107.2.1.
  
 9) SUBMIT MANUFACTURER?S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2017 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2017
 FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED
 AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS
 APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF
 INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1.
  
 10) INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE PLAN PER 2017 FBC-FUEL GAS SEC.402.1, 402.4.3
 THRU 402.6 OR 2017 FBC RES. SEC. G2413.2, G2413.4.3.
  
 11) BOTH THE WATER HEATER AND STOVE HAS GAS PIPE TO
 THEM ON SHT. P-1 BUT ON SHT. E-1 ON THE PANEL SCHDULE
 IT CALLS FOR BOTH AS ELEC POWER. PLEASE CLEARIFY. FBC
 107.2.1
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR