| Plan Review Notes For Permit 19041269 |
| Permit Number |
19041269 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-04-29 09:32:42 | PLUMBING 1ST REVIEW**DENIED** | | | | | | 1) PROVIDE HOW THE SYSTEM WAS SIZED AND IS IN | | | COMPLIANCE WITH EITHER PDI G101, PDI G102, OR FAC | | | 64E-6. FBC-P 1003.3.4 | | | | | | 2) AAV'S ARE NOT PERMITTED AS IT ALLOWS THE TANK TO | | | BECOME AIR BOUND AND THE MANUFACTURE ALSO CALLS FOR A | | | INTAKE VENT TO BE REVENTED TOGETHER AND VENT TO THE | | | OUTDOORS. FBC 1003.2, 1003.9 | | | | | | 3) P-TRAP, INLET, OUTLET, AND HORIZONTAL BRANCH SHALL | | | BE MIN 3". EACH OF THE COMPARTMENTS IS 2 DFU'S AND THE | | | HAND SINK IS ANOTHER 2DFU'S TOTALING 8 DFU'S.MAX DFU'S | | | PERMITTED ON 2" IS 6. FBC-P 710.1 | | | | | | 4) IS THIS INTERCEPTOR TO BE INSTALLED ABOVE OR BELOW | | | GROUND? FBC 107.2.1 | | | | | | | | | TIM HUNT | | | PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR | | | CITY OF WEST PALM BEACH | | | 561-248-2703 | | | [email protected] | | | THUNT@CGASOLU |
|