| 2019-05-06 12:18:24 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #19041261 |
| | 5/6/19 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PLEASE NOTE THERE ARE NO WPB BUILDING DEPARTMENT |
| | RECORDS OF LEGALLY PERMITTED AC SYSTEMS BEING INSTALLED |
| | AT THE APARTMENTS. REFER TO SECTION C503.2 FBC EC- FULL |
| | COMPLIANCE WITH THE ENERGY CODE IS REQUIRED, WHICH |
| | MEANS THAT THE FORM R402 MUST BE COMPLETELY FILLED OUT |
| | AND THREE PAGES ARE MISSING. PLEASE REVIEW THE "SCOPE" |
| | OF THE FORM LISTED IN THE TOP PRAGRAPH. IN ADDITION, |
| | PLEASE NOTE THAT THE ENERGY FORM R402 AND THE AC |
| | CALCULATIONS MUST BE SIGNED BY THE PERSON WHO PREPARED |
| | THE FORM AND THE OWNER/AGENT- SECTION R103.1.1.2 FBC |
| | EC. |
| | |
| | 2) SHEET M/P1: PROVIDE AC DUCT LAYOUT PLANS SHOWING |
| | DUCT RUNS, DUCT SIZES, AND RETURNS. PLEASE NOTE THAT |
| | ALTHOUGH THE PLAN IS INDICATING EXISTING DUCTWORK, |
| | THERE ARE NO WPB BUILDING DEPARTMENT RECORDS OF ANY |
| | PRIOR DUCT INSTALLATIONS- SECTION 107.2.1 WPB. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |