 1ST PLAN REVIEW DENIED:
  
 1. FBC B 1609.4.3 THE WIND EXPOSURE CATEGORY ON PAGES
 S-102 & S-103 INDICATE A WIND EXPOSURE OF "B". DUE TO
 LOCATION, IT APPEARS THAT THE EXPOSURE SHOULD BE "C".
 PLEASE REVIEW AND ADJUST.
  
 2. FBC B 3301 THE SAFE GUARDS DURING CONSTRUCTION NEED
 TO BE COMPLIED WITH; A SHORING PLAN WITH APPROVAL BY A
 SHORING ENGINEER (DEFERRED SUBMITTAL) WILL NEED TO BE
 SUBMITTED PRIOR TO WORK AT AREAS OF CONCERN (SUCH AS
 AREA ADJACENT TO OFFICE AREA). ALSO, INCLUDE:
 A. FBC B SECTION 3306 PROTECTION OF PEDESTRIANS.
 PROVIDE PLAN SHOWING COMPLIANCE
 B. FBC B SECTION 3307 PROTECTION OF ADJOINING PROPERTY.
 PROVIDE PLAN SHOWING COMPLIANCE.