| Plan Review Notes For Permit 19041182 |
| Permit Number |
19041182 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-05-21 11:45:20 | ***CORRECTIONS*** | | | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | 1ST PLAN REVIEW DENIED: | | | | | | 1. FBC B 1609.4.3 THE WIND EXPOSURE CATEGORY ON PAGES | | | S-102 & S-103 INDICATE A WIND EXPOSURE OF "B". DUE TO | | | LOCATION, IT APPEARS THAT THE EXPOSURE SHOULD BE "C". | | | PLEASE REVIEW AND ADJUST. | | | | | | 2. FBC B 3301 THE SAFE GUARDS DURING CONSTRUCTION NEED | | | TO BE COMPLIED WITH; A SHORING PLAN WITH APPROVAL BY A | | | SHORING ENGINEER (DEFERRED SUBMITTAL) WILL NEED TO BE | | | SUBMITTED PRIOR TO WORK AT AREAS OF CONCERN (SUCH AS | | | AREA ADJACENT TO OFFICE AREA). ALSO, INCLUDE: | | | A. FBC B SECTION 3306 PROTECTION OF PEDESTRIANS. | | | PROVIDE PLAN SHOWING COMPLIANCE | | | B. FBC B SECTION 3307 PROTECTION OF ADJOINING PROPERTY. | | | PROVIDE PLAN SHOWING COMPLIANCE. |
|