2019-06-10 14:19:28GAS 2ND REVIEW**DENIED**FL ST 553.80 (B)2B WITH RESPECT
 TO EVALUATION OF DESIGN PROFESSIONALS? DOCUMENTS, IF A
 LOCAL GOVERNMENT FINDS IT NECESSARY, IN ORDER TO
 ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING CODE AND
 ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS REQUIRED BY
 THE CODE THREE OR MORE TIMES FOR FAILURE TO CORRECT A
 CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY NOTED IN
 EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, EGRESS,
 FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW.
  
  
 1) 109.3 BUILDING PERMIT VALUATIONS. MASTER PERMIT #
 18050588 WAS NOT APPROVED FOR ANY GAS FIXTURE THEREFOR
 THE VALUE MUST INCLUDE THE COST DIFFERENCE FROM
 ELECTRIC TO GAS FOR THE TANKLESS WATER HEATER, DRYER,
 AND STOVE. THE OVEN, POOL HEATER AND BBQ MUST HAVE FULL
 VALUE LISTED AS THIS WAS NOT ON THE MASTER OR 1ST GAS
 PLAN SUBMITTED. IF, IN THE OPINION OF THE BUILDING
 OFFICIAL, THE CLAIMED VALUATIONOF BUILDING, ALTERATION,
 STRUCTURE, ELECTRICAL, GAS, MECHANICAL OR PLUMBING
 SYSTEMS APPEARS TO BE UNDERESTIMATED ON THE
 APPLICATION, THE PERMIT SHALL BE DENIED, UNLESS THE
 APPLICANT CAN SHOW DETAILED, QUANTITY ESTIMATES, AND/OR
 BONA FIDE SIGNED CONTRACTS (EXCLUDING LAND VALUE) TO
 MEET THE APPROVAL OF THE BUILDING OFFICIAL. FOR
 PERMITTING PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS
 SHALL BE TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE.
  
 2) PROVIDE AVAILABLE COMBUSTIBLE AIR. YOU ONLY PROVIDE
 WHAT IS REQUIRED. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR PER THE 2017 FBC-FUEL GAS CODE SEC.304.1, 614.6
 (CLOTHES DRYERS) OR 2017 FBC-RES. SEC. G 2407.1 AND
 G2439.4 (CLOTHES DRYERS).
  
 3) PROVIDE AVAILABLE COMBUSTIBLE AIR. YOU ONLY PROVIDE
 WHAT IS REQUIRED. SUBMIT COMBUSTION AIR CALCULATIONS
 FOR THE STOVE. WHERE COMBUSTION AIR IS PROVIDED BY THE
 BUILDING?S MECHANICAL VENTILATION SYSTEM, THE SYSTEM
 SHALL PROVIDE THE SPECIFIED COMBUSTION AIR RATE IN
 ADDITION TO THE REQUIRED VENTILATION AIR. 2017 FBC-FUEL
 GAS SEC.304.9.3 OR FBCR G2407.9.3.
  
 4) PER PLAN PROVIDE THE PRESSURE REGULATOR IS DIRECTLY
 AFTER THE METER MAKING THIS A .5 LB SYSTEM THAT IS
 UNDERSIZED. INDICATE THE DELIVERY PRESSURE (PSI) OF THE
 SYSTEM ON THE PLAN PER 2017 FBC RES. SEC. G2413.2,
 G2413.4.3.
  
 5) **NONE PROVIDE AGAIN: SUBMIT MANUFACTURER?S
 SPECIFICATION SHEETS / INSTALLATION MANUAL FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54,
 NFPA 58, AND 2017 FBC-RES. SEC. G2404.3. GAS APPLIANCES
 SHALL BE LISTED AND LABELED. THE INSTALLATION MANUALS
 FOR ALL GAS APPLIANCES / EQUIPMENT SHALL BE ONSITE AT
 THE TIME OF INSPECTION. , FBC-RES. SEC.G2408.1.\
  
 6) **NONE PROVIDE AGAIN: SUBMIT TWO COPIES OF A HOUSE
 PLAN SHOWING THE LOCATION OF THE TANKLESS WATER HEATER
 AND THE LOCATION AND DISTANCE OF ANY OPERABLE DOORS OR
 WINDOWS IN RELATION TO THE WATER HEATER. THE LOCATION
 OF THE WATER HEATER SHALL COMPLY WITH THE
 MANUFACTURER'S INSTALLATION INSTRUCTIONS. THE HOUSE
 PLAN CAN BE HAND DRAWN. WPB AMEND. TO FBC SEC. 107.2.1.
  
 7) ANSWERD
  
 8) SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS.
 A LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY
 AHEAD OF EACH MP REGULATOR.FBC-RESIDENTIAL SEC. G
 2420.4.
  
 9) SHOW THE DISTANCE FROM THE 2 PSI REGULATOR TO THE
 APPLIANCE. COMPLY WITH 2017 FBC-FUEL GAS SEC. 402.4.1
 OR 2017 FBC-RES. SEC. G2413.4.1, G2413.4.2 FOR THE
 PROPER PIPE SIZE AND BTU LOAD
  
 10) SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE
 CORRUGATED STAINLESS STEEL TUBING (IF APPLICABLE) FOR
 EACH PIPE SIZE. WPB AMENDMENTS TO FBC SEC.107.2.1.
  
 NEW COMMENT:
  
 11) THIS PLAN IS NOW SHOWING A BBQ GRILL. IS THIS UNDER
 A COVERED AREA? FBC 107.2.1
  
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR
 CITY OF WEST PALM BEACH