| 2019-04-24 16:40:01 | GAS 1ST REVIEW**DENIED** |
| | |
| | 1) 109.3 BUILDING PERMIT VALUATIONS. MASTER PERMIT # |
| | 18050588 WAS NOT APPROVED FOR ANY GAS FIXTURE THEREFOR |
| | THE VALUE MY INCLUDE THE COST DIFFERENCE FROM ELECTRIC |
| | TO GAS FOR THE TANKLESS WATER HEATER, DRYER, AND STOVE. |
| | IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE |
| | CLAIMED VALUATIONOF BUILDING, ALTERATION, STRUCTURE, |
| | ELECTRICAL, GAS, MECHANICAL OR PLUMBING SYSTEMS APPEARS |
| | TO BE UNDERESTIMATED ON THE APPLICATION, THE PERMIT |
| | SHALL BE DENIED, UNLESS THE APPLICANT CAN SHOW |
| | DETAILED, QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED |
| | CONTRACTS (EXCLUDING LAND VALUE) TO MEET THE APPROVAL |
| | OF THE BUILDING OFFICIAL. FOR PERMITTING PURPOSES, |
| | VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL |
| | REPLACEMENT VALUE TO INCLUDE STRUCTURAL, ELECTRIC, |
| | PLUMBING, MECHANICAL, INTERIOR FINISH, RELATIVE SITE |
| | WORK, ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS, |
| | OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. |
| | |
| | 2) SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2017 |
| | FBC-FUEL GAS CODE SEC.304.1, 614.6 (CLOTHES DRYERS) OR |
| | 2017 FBC-RES. SEC. G 2407.1 AND G2439.4 (CLOTHES |
| | DRYERS). |
| | |
| | 3) SUBMIT COMBUSTION AIR CALCULATIONS FOR THE STOVE. |
| | WHERE COMBUSTION AIR IS PROVIDED BY THE BUILDING?S |
| | MECHANICAL VENTILATION SYSTEM, THE SYSTEM SHALL PROVIDE |
| | THE SPECIFIED COMBUSTION AIR RATE IN ADDITION TO THE |
| | REQUIRED VENTILATION AIR. 2017 FBC-FUEL GAS SEC.304.9.3 |
| | OR FBCR G2407.9.3. |
| | |
| | 4) INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM |
| | ON THE PLAN PER 2017 FBC RES. SEC. G2413.2, G2413.4.3. |
| | |
| | 5) SUBMIT MANUFACTURER?S SPECIFICATION SHEETS / |
| | INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY |
| | COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND 2017 |
| | FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED |
| | AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS |
| | APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF |
| | INSPECTION. , FBC-RES. SEC.G2408.1.\ |
| | |
| | 6) SUBMIT TWO COPIES OF A HOUSE PLAN SHOWING THE |
| | LOCATION OF THE TANKLESS WATER HEATER AND THE LOCATION |
| | AND DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN |
| | RELATION TO THE WATER HEATER. THE LOCATION OF THE WATER |
| | HEATER SHALL COMPLY WITH THE MANUFACTURER'S |
| | INSTALLATION INSTRUCTIONS. THE HOUSE PLAN CAN BE HAND |
| | DRAWN. WPB AMEND. TO FBC SEC. 107.2.1. |
| | |
| | 7) YOU ONLY PROVIDE 1 SIZING TABLE BUT SHOW 3 DIFFERENT |
| | PIPING MATERIALS. SUBMIT TWO COPIES OF THE APPLICABLE |
| | SIZING TABLES USED TO SIZE THE GAS SYSTEM OR PLACE A |
| | NOTE ON THE PLANS/DRAWINGS SPECIFYING WHICH SIZING |
| | TABLE(S) FROM THE GAS CODE OR OTHER STANDARD THAT WERE |
| | USED IN THE DESIGN OF THIS GAS SYSTEM. REFER TO THE |
| | 2017 FBC-RES. SEC. G2413.3, G2412.8, G2413.1, G2413.2, |
| | & G2413 |
| | |
| | 8) SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS. |
| | A LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY |
| | AHEAD OF EACH MP REGULATOR.FBC-RESIDENTIAL SEC. G |
| | 2420.4. |
| | |
| | 9) SHOW THE DISTANCE FROM THE 2 PSI REGULATOR TO THE |
| | APPLIANCE. COMPLY WITH 2017 FBC-FUEL GAS SEC. 402.4.1 |
| | OR 2017 FBC-RES. SEC. G2413.4.1, G2413.4.2 FOR THE |
| | PROPER PIPE SIZE AND BTU LOAD |
| | |
| | 10) SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL |
| | PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE |
| | CORRUGATED STAINLESS STEEL TUBING (IF APPLICABLE) FOR |
| | EACH PIPE SIZE. WPB AMENDMENTS TO FBC SEC.107.2.1. |
| | |
| | |