Plan Review Notes For Permit 19041099
Permit Number 19041099
Review Stop P
Sequence Number 1
Notes
Date Text
2019-04-23 15:37:41PLUMBING 1ST REVIEW**DENIED**PROVIDE 2 COPIES FOR EACH
 PERMIT APPLICATION
  
 1) PLANS THAT BEAR THE TITLE BLOCK OF A DESIGN
 PROFESSIONAL SHALL BE SIGNED AND SEALED. FAC
 61G1-16.001
  
 2) PLAN DOES NOT SHOW PIPE SIZE OF MAIN LINE OR GPM
 REQUIREMENTS ON THE SYSTEM. FBC 107.2.1
  
 3) CITY RECORD DO NOT SHOW AN EXISTING PERMITTED
 BACKFLOW OR IRRAGATION SYSTMEM. PROVIDE THE BACKFLOW
 MAKE, MODEL , AND SIZE. IS THIS A SEPERATE IRRAGATION
 METER FEEDING THIS SYSTEM? PLEASE CLARIFY. FBC 107.3.5.
 WPB CROSS CONNECTION MANUAL.
  
 4) VALUE SEEMS LOW. PROVIDE A BONA FIDE SIGNED
 CONTRACT. 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE
 OPINION OF THE BUILDING OFFICIAL, THE CLAIMED VALUATION
 OF BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED,
 QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS
 (EXCLUDING LAND VALUE) TO MEET THE APPROVAL OF THE
 BUILDING OFFICIAL. FOR PERMITTING PURPOSES, VALUATION
 OF BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT
 VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING,
 MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK,
 ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR
 CITY OF WEST PALM BEACH
 561-248-2703
 [email protected]