| Date |
Text |
| 2019-10-10 09:29:40 | JONATHAN BROOKS JR. |
| | BUILDING PLANS EXAMINER |
| | WORK HOURS TUESDAY & THURSDAY 7:00 AM TO 3:00 PM |
| | (561) 805-6716 ALTERNATE: CONTACT SAMANTHA HILL (561) |
| | 805-6724 |
| | [email protected] |
| | |
| | 1ST REVIEW: FBC 2017 6TH EDITION |
| | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| | FBC B = FBC BUILDING |
| | FBC R = FBC RESIDENTIAL |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | YOU MAY RESUBMIT PRINTABLE DOCUMENTS ALONG WITH A |
| | COMPLETED RESUBMITTAL FORM, VIA EMAIL TO |
| | [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT |
| | NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE |
| | RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE: |
| | HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B |
| | UILDING-PERMIT-FORMS |
| | |
| | 1.FBC B 107.2.1. PLEASE PROVIDE THE FOLLOWING |
| | ADDITIONAL INFORMATION ON SUBMITTED DRAWINGS: |
| | CONSTRUCTION TYPE; OCCUPANCY GROUP; CLASSIFICATION OF |
| | WORK (ADDITION); BUILDING HEIGHT. SECOND REQUEST. |
| | 2.FBC B 107.2.1 PROVIDE A DRAWING DETAIL SHOWING |
| | INTERSECTION OF NEW STORAGE ROOM ROOF WITH EXISTING |
| | LAUNDRY ROOM ROOF/WALL WITH FLASHING (IF APPLICABLE); |
| | ALONG WITH DRAWING DETAILS OF THE CONSTRUCTION METHOD |
| | USED OF MATING NEW STORAGE ROOM ROOF, WALLS, FOOTINGS, |
| | SLAB, COLUMNS AND BEAMS TO THE EXISTING RESIDENTIAL |
| | STRUCTURE. SECOND REQUEST. |
| | 3.FBC B 107.2.1. REVISE ELEVATION DETAIL DRAWINGS TO |
| | SHOW EXISTING RESIDENTIAL STRUCTURE AND NEW PROPOSED |
| | STORAGE ROOM TOGETHER. |
| | 4.FBC B 107.2.1. SUBMITTED MIAMI-DADE NOA 16-0808.14 |
| | AND MIAMI-DADE NOA 18-1109.03 ARE BOTH UNDERLAYMENT?S; |
| | PROVIDE TWO SETS OF PRODUCT APPROVALS/NOA?S FOR AN |
| | APPROVED ROOF ASSEMBLY FOR A FLAT WOOD DECK ASSEMBLY. |
| | ALL APPLICABLE DETAILS AND ATTACHMENTS MUST BE CLEARLY |
| | IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. DETAILS |
| | AND ATTACHMENTS NOT SPECIFICALLY COVERED IN PRODUCT |
| | APPROVALS WILL NEED SITE-SPECIFIC ENGINEERING. AS PER |
| | RULE 61G20-3 |
| | 5. FBC B 105.1. SEPARATE PERMIT APPLICATION REQUIRED |
| | FOR ROOF WORK. |
| | |