| 2019-05-14 06:52:50 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. SHOW ALL ELECTRICAL WORK TO BE PERFORMED ON THE |
| | SUBMITTED PLANS. A NOTE STATING "KITCHEN COUNTERTOP |
| | RECEPTACLES WILL BE PER CODE" WILL NOT SUFFICE. FBC |
| | 107.2.1 NEC 210.52 |
| | |
| | 2. KITCHEN COUNTERTOP RECEPTACLES SPACING IS NOT CODE |
| | COMPLIANT.PLEASE PROVIDE CORRECTION. NEC 210.52C |
| | |
| | 3. PLAN PROVIDED IS A COPY. PLANS SUBMITTED MUST HAVE |
| | ORIGINAL SIGNATURES ON PLAN. ELECTRICAL PLAN IS |
| | REQUIRED TO BE SIGNED BY PERSON RESPONSIBLE FOR THE |
| | DESIGN. PROVIDE CORRECTION. FS 481.229; WPB FBC |
| | 107.2.1, 107.3.5.1.2 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | CODES IN EFFECT: |
| | |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2017 6TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | V/R, |
| | |
| | FRANK GIAQUINTO III |
| | ELECTRICAL INSPECTOR |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | [email protected] |
| | CELL: 561-657-1653 |
| | |