Plan Review Notes
Plan Review Notes For Permit 19040999
Permit Number 19040999
Review Stop P
Sequence Number 1
Notes
Date Text
2019-04-24 11:44:47PLUMBING 1ST REVIEW**DENIED**
  
 1) SUB PLUMBING DEMO PERMIT REQUIRED. FBC 105.1
  
 2) IT IS NOT CLEAR ON YOUR INTENT OF PLUMBING DEMO WORK
 BEING PERFORMED. PROVIDE A NARRATIVE OF WHAT IS BEING
 REMOVED AND CAPPED OFF AND WHAT IS TO REMAIN. REMOVE
 PROJECT NOTES #2,3,4,5 AS THIS IS STATING WHAT NEW WORK
 IS BEING PERFORMED AND THIS PLAN AND PERMIT IS FOR DEMO
 ONLY AND IS MIS-LEADING. FBC 107.2.1
  
 3) PROVIDE WORKERS BATHROOM LOCATION. FBC-PLUMBING
 311.1
  
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR