| 2019-05-15 08:19:46 | 2ND REVIEW FBC-2017 MECHANICAL |
| | PERMIT #19040969 |
| | 5/15/19 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PLEASE LABEL THE AIR HANDLERS AH-1 & AH-2, AND |
| | PROVIDE EQUIPMENT SCHEDULES FOR EACH ON THE PLAN- |
| | SECTION 107.2.1 WPB |
| | |
| | 2) THE PLANS DO NOT MATCH THE MAIN BUILDING PLANS: A) |
| | GUEST BEDROOM #2 IS LABELED AS AN OFFICE. B) WALKIN |
| | CLOSET MISSING IN GUEST BEDROOM #2. C) OFFICE BY LIVING |
| | ROOM IS MISLABELED AS FAMILY ROOM- SECTION 107.2.1 WPB. |
| | |
| | 3) THE RETURN AIR FROM THE BEDROOMS VIA THE 12X12 |
| | GRILLES APPEARS TO BE RESTRICTED FROM RETURNING TO |
| | ETIHER THE MAIN RETURNN GRILLES IN THE HALLWAYS AND TO |
| | THE AIR HANDLERS- SECTION 601.6 FBC M. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |