| Date |
Text |
| 2019-05-20 16:43:15 | 2ND REVIEW FBC-2017 MECHANICAL |
| | PERMIT #19040495 |
| | 5/20/19 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | THE 1ST REVIEW COMMENTS #2, 3, & 4 PRINTED BELOW STILL |
| | EXIST- PLEASE COMPLY. |
| | |
| | 2) SHEET 1: PLEASE PROVIDE A SCOPE OF WORK FOR |
| | MECHANICAL WITH CORRELATING DRAWINGS AND DETAILS ON THE |
| | PLAN. |
| | |
| | 3) SHEET 1: IDENTIFY ALL NEW COOKING APPLIANCES ON THE |
| | PLAN AND SUBMIT MANUFACTURER'S SPECIFICATIONS- SECTION |
| | 917.2 FBC M. |
| | |
| | 4) SHEET 1: CLARIFY IF A NEW KITCHEN EXHAUST HOOD AND |
| | EXHAUST DUCT ARE TO BE INSTALLED AND SUBMIT |
| | MANUFACTURER'S SPECIFICATIONS. SHOW THE EXHAUST DUCT |
| | RUN AND TERMINATION LOCATION ON THE PLAN. PLEASE NOTE |
| | MAKEUP AIR MAYBE REQUIRED PER SECTION 505.2 FBC M. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |