| 2019-09-23 14:49:42 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| | FBC B = FBC BUILDING |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | FBC R = FBC RESIDENTIAL |
| | |
| | COMMENTS FROM PREVIOUS LIST: |
| | |
| | 1. PLAN TO BE REVISED TO NOTE COMPLIANCE WITH FBC 2017; |
| | REMOVE REFERENCES TO PREVIOUS CODES AND STAFF. |
| | |
| | 2ND REVIEW: THIS WAS DONE, BUT THE FOLLOWING ISSUES |
| | WERE FOUND: |
| | |
| | LS1, BUILDING CODE SUMMARY 2, SEE FBC B 602.4, THIS |
| | BUILDING IS NOT HEAVY TIMBER TYPE IVB, REVISE. |
| | LS1, BUILDING CODE SUMMARY 5, SEE FBC B 302, EACH AREA |
| | IS TO BE CLASSIFIED AS TO OCCUPANCY CLASSIFICATION |
| | ("MIXED" IS NOT ONE OF THE CLASSIFICATIONS). THIS |
| | APPEARS TO BE BUSINESS AND A3 ON THE FIRST FLOOR, R2 ON |
| | THE SECOND FLOOR. REVISE SECTION 5 TO CLARIFY. |
| | LS1, BUILDING CODE SUMMARY 6, PROPOSED HEIGHT IS 1 |
| | STORY; ISN'T THIS A 2 STORY BUILDING? |
| | LS1, BUILDING CODE SUMMARY 7, FLOOR CONSTRUCTION IS 0 |
| | HOURS. AN OCCUPANCY SEPARATION BETWEEN RESIDENTIAL AND |
| | OTHER OCCUPANCIES IS REQUIRED AND WAS REQUIRED WHEN THE |
| | BUILDING WAS CONSTRUCTED, REVISE TO REFLECT SEPARATION |
| | REQUIREMENT. |
| | |
| | 2-3. OK |
| | |
| | 4. ONE BATHROOM ON THE 1ST FLOOR IS NOT ACCESSIBLE AND |
| | THE ENTRY DOORS TO THE MEDITATION ROOM ARE NOT |
| | ACCESSIBLE; APPLICANT TO DOCUMENT THAT THIS IS NOT |
| | REQUIRED DUE TO DISPROPORTIONATE COST. THIS MAY BE SENT |
| | VIA EMAIL FOR PRELIMINARY REVIEW. |
| | |
| | 2ND REVIEW, IT IS NOT CLEAR HOW THIS WAS ADDRESSED. |
| | |
| | 5-9. OK |
| | |
| | 10. LIFE SAFETY AND ARCHITECTURAL SHEETS TO BE PREPARED |
| | BY AN ARCHITECT OR ENGINEER WILL OBTAIN A DETERMINATION |
| | FROM FBPE OR FLORIDA BOARD OF ARCHITECTS. |
| | |
| | 2ND REVIEW, IT IS NOT CLEAR HOW THIS WAS ADDRESSED. |
| | |
| | |
| | |