Date Text
2019-09-21 13:15:472ND REVIEW: 19040938
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. THE BREAK ROOM SINK SHALL COMPLY WITH FBC ACC 212.2,
 804,
 606.2 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE COMPLYING
 WITH 305, POSITIONED FOR A FORWARD APPROACH, AND KNEE
 AND TOE CLEARANCE COMPLYING WITH 306 SHALL BE PROVIDED.
 EXCEPTIONS:1.A PARALLEL APPROACH COMPLYING WITH 305
 SHALL BE PERMITTED TO A KITCHEN SINK, IN A SPACE WHERE
 A COOK TOP OR CONVENTIONAL RANGE IS NOT PROVIDED, AND
 TO WET BARS.
 606.3 HEIGHT. LAVATORIES AND SINKS SHALL BE INSTALLED
 WITH THE FRONT OF THE HIGHER OF THE RIM OR COUNTER
 SURFACE 34 INCHES (865 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND.
  
 2. THE SINGLE USER BATHROOM ON THE FIRST FLOOR SHALL
 COMPLY WITH FBC ACC 213.2, 213.3.2, 213.3.4
 604.3.1 SIZE. CLEARANCE AROUND A WATER CLOSET SHALL BE
 60 INCHES (1525 MM) MINIMUM MEASURED PERPENDICULAR FROM
 THE SIDE WALL AND 56 INCHES (1420 MM) MINIMUM MEASURED
 PERPENDICULAR FROM THE REAR WALL.
 606.2 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE COMPLYING
 WITH 305, POSITIONED FOR A FORWARD APPROACH, AND KNEE
 AND TOE CLEARANCE COMPLYING WITH 306 SHALL BE PROVIDED.
  
 3. GRAB BARS SHALL BE MEASURED TO THE TOP OF THE
 GRIPPING SURFACE FROM FINISHED FLOOR. PER FBC ACC 609.4
  
 4. SHT S-2 DETAIL #1 THE PLUMBING FIXTURE CLEARANCES
 SHALL COMPLY FBC PL
 405.3.1 WATER CLOSETS, URINALS, LAVATORIES AND BIDETS.
 A WATER CLOSET, URINAL, LAVATORY OR BIDET SHALL NOT BE
 SET CLOSER THAN 15 INCHES (381 MM) FROM ITS CENTER TO
 ANY SIDE WALL, PARTITION, VANITY OR OTHER OBSTRUCTION,
 OR CLOSER THAN 30 INCHES (762 MM) CENTER TO CENTER
 BETWEEN ADJACENT FIXTURES. THERE SHALL BE NOT LESS THAN
 A 21-INCH (533 MM) CLEARANCE IN FRONT OF THE WATER
 CLOSET, URINAL, LAVATORY OR BIDET TO ANY WALL, FIXTURE
 OR DOOR. WATER CLOSET COMPARTMENTS SHALL BE NOT LESS
 THAN 30 INCHES (762 MM) IN WIDTH AND NOT LESS THAN 60
 INCHES (1524 MM) IN DEPTH FOR FLOOR MOUNTED WATER
 CLOSETS AND NOT LESS THAN 30 INCHES (762 MM) IN WIDTH
 AND 56 INCHES (1422 MM) IN DEPTH FOR WALL-HUNG WATER
 CLOSETS. THE DISTANCE BETWEEN THE CENTER OF THE SHOWER
 AND THE CENTER OF THE LAVATORY AND FROM THE CENTER OF
 THE LAVATORY TO THE CENTER OF THE TOILET SHALL BE A MIN
 OF 30".
  
 5. SHT. G-1 THE SANITARY ISOMETRIC DRAWING, NO OTHER
 FIXTURE SHALL CONNECT TO THE WET VENT OF A BATHROOM
 GROUP OTHER THAN 2 TOILETS 2 LAVATORY'S AND 2 TUB OR
 SHOWER'S. THE URINAL IN THE MENS BATHROOM SHALL CONNECT
 DOWN STREAM OF THE BATHROOM GROUP.IN THE LAUNDRY ROOM
 ON THE FIRST FLOOR THE SERVICE SINK SHALL CONNECT DOWN
 STREAM OF THE BATHROOM GROUP. PER FBC PL 912.1
  
 6. THE VENT ON THE TOILET IN THE SINGLE USER BATHROOM
 ON THE FIRST FLOOR IS A HORIZONTAL DRY VENT NOT
 APPROVED, ALL VENTS SHALL CONNECT TO THE TOP OF THE
 HORIZONTAL PIPE AND RUN VERTICALLY UP TO A POINT ABOVE
 FLOOD LEVEL RIM OF THE FIXTURE. PER FBC PL 905.3, 905.4
  
 7. ON THE HOT WATER SYSTEM IF THE FURTHEST FIXTURE IS
 MORE THAN 50' FROM THE SOURCE OF HOT WATER A
 RECIRCULATING SYSTEM IS REQUIRED IT APPEARS THAT ONE OF
 THE BATHROOMS UPSTAIRS MAY BE OVER 50" .
 PER FBC PL 607.2
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]