| 2019-07-31 06:13:19 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| | FBC B = FBC BUILDING |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | FBC R = FBC RESIDENTIAL |
| | |
| | THIS IS A RECAP OF MEETING ON 7/30/19 WHEREIN DESIGN |
| | OPTIONS WERE DISCUSSED. FOR CODE REFERENCES, PLEASE SEE |
| | PREVIOUS BUILDING REVIEW. NOTE THAT ANY DESIGN WHICH |
| | COMPLIES WITH THE FBC/FFPC IS ACCEPTABLE; THE BELOW IS |
| | ONE DESIGN OPTION DISCUSSED IN THE MEETING WITH |
| | ENGINEER, OWNER AND CONTRACTOR. |
| | |
| | 1. PLAN TO BE REVISED TO NOTE COMPLIANCE WITH FBC 2017; |
| | REMOVE REFERENCES TO PREVIOUS CODES AND STAFF. |
| | |
| | 2. WORK AREA (SEE DEFINITION IN FBC 2017 EB) TO BE |
| | MODIFIED TO CLEARLY DEMONSTRATE THAT A LEVEL II |
| | ALTERATION IS PROPOSED; WORK AREA REDUCED ACCORDINGLY. |
| | |
| | 3. 2ND FLOOR, CURRENTLY R2, UNDER THIS OPTION WOULD |
| | REMAIN R2 (NO CHANGE OF OCCUPANCY), PLAN TO BE MODIFIED |
| | TO CLARIFY; ACCESSIBILITY FOR 2ND FLOOR NOT REQUIRED |
| | (SEE DEFINITION OF PLACE OF PUBLIC ACCOMMODATION). |
| | |
| | 4. ONE BATHROOM ON THE 1ST FLOOR IS NOT ACCESSIBLE AND |
| | THE ENTRY DOORS TO THE MEDITATION ROOM ARE NOT |
| | ACCESSIBLE; APPLICANT TO DOCUMENT THAT THIS IS NOT |
| | REQUIRED DUE TO DISPROPORTIONATE COST. THIS MAY BE SENT |
| | VIA EMAIL FOR PRELIMINARY REVIEW. |
| | |
| | 5. PER FIRE, A FIRE ALARM SYSTEM WILL BE INSTALLED. |
| | |
| | 6. A REMOTELY LOCATED EXIT IS TO BE INSTALLED FOR THE |
| | FIRST FLOOR MEDITATION AREA; IT IS ACCEPTABLE FOR THE |
| | MEANS OF EGRESS TO GO THROUGH THE ADJACENT ACCESSORY |
| | AREA. |
| | |
| | 7. FOR ACCESSIBILITY TO THE PRIMARY FUNCTION AREA, ALL |
| | FIRST FLOOR DOORS TO BE MODIFIED TO MAINTAIN 18" |
| | CLEARANCE ON PULL SIDE TO COMPLY WITH ACCESSIBILITY. |
| | |
| | 8. OCCUPANT LOAD IN THE MEDITATION AREATO BE REDUCED |
| | (INCLUDES TABLES AND CHAIRS). |
| | |
| | 9. PER FIRE, ONLY ONE LIGHTWEIGHT ROOF CONSTRUCTION ID |
| | SIGN IS REQUIRED AT THE MAIN ENTRY; OTHERS ARE |
| | OPTIONAL. |
| | |
| | 10. LIFE SAFETY AND ARCHITECTURAL SHEETS TO BE PREPARED |
| | BY AN ARCHITECT OR ENGINEER WILL OBTAIN A DETERMINATION |
| | FROM FBPE OR FLORIDA BOARD OF ARCHITECTS. |
| | |
| | |
| | |
| | |