| 2019-05-09 13:43:13 | 1ST REVIEW: 19040938 |
| | |
| | 2017 FLORIDA BUILDING CODE 6TH EDITION |
| | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| | EDITION |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. THE EXCEPTION FROM THE FBC EXISTING 301.1 IS FOR THE |
| | STRUCTURAL REQUIREMENTS ALL THE NEW PLUMBING AND GAS |
| | SHALL COMPLY WITH THE FBC PL 2017 6TH EDITION. |
| | |
| | 2. SHT LS-1 UNDER THE PLUMBING FIXTURE FOR THE FIRST |
| | FLOOR IT LIST 3 LAVATORY'S FOR MALE THE PLAN ONLY SHOWS |
| | 1 FORE THE WOMEN IT LIST 3 TOILETS AND 3 LAVATORY'S THE |
| | PLAN ONLY SHOWS 2 INCLUDING THE UNISEX NEXT TO THE |
| | BREAK ROOM PLEASE CLARIFY SHALL COMPLY WITH FBC PL |
| | TABLE 403.1 |
| | |
| | 3. SHT. P-1 ALL NEW PLUMBING PLUMBING PIPING AND |
| | FIXTURES SHALL COMPLY WITH FBC PL 2017 6TH EDITION |
| | |
| | 4. SHT G-1 THE SANITARY ISOMETRIC DRAWING HAS THE |
| | FOLLOWING CODE VIOLATIONS PLEASE REVISE. PER WPB AMEND |
| | TO FBC 107.2.1 |
| | A) THE NEW WATER FOUNTAIN SHALL CONNECT TO THE BUILDING |
| | DRAIN DOWN STREAM OF THE BATHROOM GROUP. FBC PL 912.1 |
| | B) THE NEW WATER FOUNTAIN IS NOT VENTED PROVIDE |
| | VENTING. FBC PL 910.1 |
| | C) REMOVE FIXTURES FROM ISOMETRIC IT IS TO CONGESTED TO |
| | DETERMINE CODE COMPLIANCE. |
| | D) ON THE SECOND FLOOR THE WASHING MACHINE APPEARS TO |
| | BE TIED INTO THE TOILET THAT WAS DEMOED REMOVE ALL OLD |
| | FIXTURES AND CONNECTION PIPING. |
| | E) ON THE SECOND FLOOR THE LAUNDRY'S AND THE KITCHEN |
| | SHALL CONNECT DOWN STREAM OF THE BATHROOM GROUPS. FBC |
| | PL 912.1, 912.1.1 |
| | F) GOOSENECK FITTING ARE NOT APPROVED FITTINGS P-TRAPS |
| | ARE THE APPROVED CONNECTION. PER WPB AMEND TO FBC |
| | 107.2.1 |
| | G) THE LAUNDRY AND KITCHEN ON THE FIRST FLOOR SHALL |
| | CONNECT DOWN STREAM OF ANY BATHROOM GROUP. FBC PL 912.1 |
| | |
| | 5. PROVIDE A WATER ISOMETRIC DRAWING. PER WPB AMEND TO |
| | FBC 107.2.1 |
| | |
| | 6. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES |
| | AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET |
| | FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND |
| | VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN |
| | APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT |
| | CONFORMS TO ASSE 1070 OR CSA B125.3. PER FBC 416.5 |
| | |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |