| 2019-05-15 10:50:44 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #19040938 |
| | 5/15/2019 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE LOUVERED AC CLOSET DOORS SHALL BE |
| | NON-COMBUSTIBLE IN ACCORDANCE WITH SECTION 602.2 AND |
| | 606.2.2.1 FBC M . THE DOOR SCHEDULE INDICATES THE DOORS |
| | ARE WOOD. |
| | |
| | 2) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE DRYERS- |
| | SECTION 504.1 FBC M. PROVIDE A 100 SQ. IN. MAKEUP AIR |
| | OPENING FOR THE CLOSETS THAT ARE ENCLOSING DRYERS- |
| | SECTION 504.6 |
| | |
| | 3) SUBMIT MANUFACTURER'S SPECIFCATIONS FOR THE RANGE |
| | AND RANGE HOOD- SECTIONS 917.1 AND 505.1 FBC M . PLEASE |
| | SEE SECTION 505.2 FOR MAKEUP AIR REQUIREMENTS FOR THE |
| | HOOD. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |