| 2019-05-08 10:24:17 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) SHEET C 1.1, A 101 & 102 - THERE ARE INDICATIONS OF |
| | A NEW GATE WITH INGRESS-EGRESS LANES. THERE LANE ARE |
| | INDICATED WITH DIMENSIONS LESS THAN THE REQUIRED |
| | 20'(2'9" INGRESS AND 13'6" EGRESS) FIRE LANES FOR FIRE |
| | DEPARTMENT APPARATUS ACCESS. |
| | |
| | PER NFPA 1 |
| | |
| | 18.2.3.4 SPECIFICATIONS. |
| | 18.2.3.4.1 DIMENSIONS. |
| | 18.2.3.4.1.1 FIRE DEPARTMENT ACCESS ROADS SHALL HAVE AN |
| | UNOBSTRUCTED |
| | WIDTH OF NOT LESS THAN 20 FT (6.1 M). |
| | |
| | PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC CODE |
| | REFERENCES. |
| | |
| | |
| | |
| | 2) SHEET C 1.1, A 101 & 102 - THERE ARE INDICATIONS OF |
| | A NEW GATE WITH INGRESS-EGRESS LANES. GATES ARE |
| | REQUIRED TO BE ACCESSIBLE FOR THE FD. |
| | |
| | 18.2.2* ACCESS TO STRUCTURES OR AREAS. |
| | 18.2.2.1 ACCESS BOX(ES). THE AHJ SHALL HAVE THE |
| | AUTHORITY TO REQUIRE |
| | AN ACCESS BOX(ES) TO BE INSTALLED IN AN ACCESSIBLE |
| | LOCATION WHERE |
| | ACCESS TO OR WITHIN A STRUCTURE OR AREA IS DIFFICULT |
| | BECAUSE OF SECURITY. |
| | THE ACCESS BOX(ES) SHALL BE OF AN APPROVED TYPE LISTED |
| | IN ACCORDANCE |
| | WITH UL 1037. |
| | |
| | A KNOX KEY SWITCH SYSTEM IS RECOMMENDED. |
| | |
| | PLEASE REVIEW AND PROVIDE AN APPLICABLE NOTE OF |
| | ACKNOWLEDGEMENT. |
| | |
| | |
| | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |