Plan Review Notes
Plan Review Notes For Permit 19040937
Permit Number 19040937
Review Stop B
Sequence Number 1
Notes
Date Text
2019-04-24 11:39:55BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 JOSEAN A. DUPREY E.I., BN, PX
 BUILDING PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6716
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE GEOTECHNICAL REPORT. THE SOIL COMPACTION
 REQUIREMENT IS NOT SPECIFY ON THE STRUCTURAL DRAWINGS.
 THE GENERAL NOTES ONLY MAKE REFERENCE TO THE
 GEOTECHNICAL REPORT. FBC 107
  
 2. THE DRAWING SHEET S-100 DETAIL #2 SHOW THE
 CONNECTION BETWEEN THE PRE-CAST COLUMN AND FOUNDATION
 APPEARS TO BE THRU ANCHOR BOLTS AND STEEL PLATE.
 HOWEVER SPECIFICATIONS FOR THIS ANCHOR BOLTS AND PLATES
 WERE NOT PROVIDED. PLEASE PROVIDE STEEL GRADE,
 DIAMETER, AND DIMENSIONS FOR THE CONNECTION. FBC 107
  