Plan Review Notes
Plan Review Notes For Permit 19040847
Permit Number 19040847
Review Stop E
Sequence Number 2
Notes
Date Text
2019-06-04 13:37:51CHANGED POOL HEATER FROM ELECTRIC HEAT PUMP TO NATURAL
 GAS.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved