| Plan Review Notes For Permit 19040847 |
| Permit Number |
19040847 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-05-02 10:37:16 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY ELECTRICAL | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE PLANS SPECIFY A 60 AMP POOL SUB-PANEL WITH A 2 | | | POLE 20 AMP BREAKER FOR A GAS POOL HEATER. THE | | | SPECIFICATIONS FOR A 6.37 KW ELECTRIC HEAT PUMP WAS | | | SUBMITTED. PLEASE COORDINATE THE PLANS WITH THE POOL | | | HEATER SPECIFICATIONS. FBC 107.2.1 | | | | | | 2) SUBMIT TWO SETS OF ELECTRICAL LOAD CALCULATIONS FOR | | | THE EXISTING HOUSE TO SHOW THAT THE EXISTING PANEL IS | | | ADEQUATE. THE NAME AND SIGNATURE OF THE PERSON | | | RESPONSIBLE IS REQUIRED ON THE CALCULATION DOCUMENTS. | | | FBC E3401.4 | | | | | | 3) AN ELECTRICAL POOL SUB-PERMIT IS REQUIRED. FBC 105.1 | | | |
|