 DENIED BY ELECTRICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE PLANS SPECIFY A 60 AMP POOL SUB-PANEL WITH A 2
 POLE 20 AMP BREAKER FOR A GAS POOL HEATER. THE
 SPECIFICATIONS FOR A 6.37 KW ELECTRIC HEAT PUMP WAS
 SUBMITTED. PLEASE COORDINATE THE PLANS WITH THE POOL
 HEATER SPECIFICATIONS. FBC 107.2.1
  
 2) SUBMIT TWO SETS OF ELECTRICAL LOAD CALCULATIONS FOR
 THE EXISTING HOUSE TO SHOW THAT THE EXISTING PANEL IS
 ADEQUATE. THE NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE IS REQUIRED ON THE CALCULATION DOCUMENTS.
 FBC E3401.4
  
 3) AN ELECTRICAL POOL SUB-PERMIT IS REQUIRED. FBC 105.1
  